“Quick Start” Guide

IMPORTANT PRE-START CHECKS: Follow boiler fill (and other) instructions in the ALTA Boiler Installation, Operating and Service instructions 

(I,O&S). Inspect all water lines, gas lines, wiring, venting and associated connections. Follow instructions to purge all air from the heat 

exchanger and system piping with the hose provided. Do not install any boiler SKU ending with “02” over 2,000 ft. (610m) altitude. (Example: 

ALTA-120-1G02). Only boiler SKUs with -00 suffixes may be installed at altitudes between 2,000 ft. (610m) and 10,100 ft. (3,079m) - 

Example: ALTA-120-1G00. 

TIME-SAVING NOTE: Gas valve throttle screw and offset adjustments are not required for start up. This boiler adapts to heating requirements with a 

self-calibrating, “gas adaptive” control that monitors flame ionization to automatically adjust the gas valve to a correct air-fuel ratio.  

Start a call for central heat (CH) and 

observe the display.

NOTE: Boiler fires ten seconds after CH call. 

If it does not light after two tries, the boiler 

will enter a “soft lockout” for one hour. For 

fast reset: 

•  Interrupt power for three seconds

•  Re-connect power and restart

•  Press      button to reset

•  Watch for flame icon

During CH call

(While running)

1.

2.

Check gas pressure at valve inlet test port. 

Verify that the inlet gas pressure is between the 

minimum and maximum gas pressures shown on 

the rating plate when operating at maximum gas 

input rate and when all gas appliances (including 

the boiler) are both on and off. 

GAS PRESSURE REQUIREMENTS (0-2,000 ft. only)

Max: 14.0 in.wc

Min: 2.5 in.wc (natural gas), 8.0 in.wc (L.P. gas)

4.

Safety Check: Ignition Safety Shut-Off 
•   When boiler is running, carefully unplug black electrode/

flame sensor wire at burner door using insulated pliers

•  The burner should shut off immediately
•  Reconnect black electrode/flame sensor wire

3.

Safety Check: Combustion

•  Verify boiler is running over 50% firing rate

•  Close boiler front door and wait five minutes

•  Insert combustion analyzer probe into test port 

•  Measure carbon monoxide (CO)

•  If CO is under 200ppm, combustion check is complete 

•  If CO exceeds 200ppm, follow troublehooting in I,O&S

•  Replace test port cap into test port

Without a CH call

(Stand-by)

Flame icon appears 

last, after start up 

protocol is complete 

and after boiler is 

running. 

reset lockout



Model ALTA-120, ALTA-150, ALTA-180

High Efficiency Condensing Boiler

Press 

buttons 

to adjust 

parameters

+

Press 

buttons to 

view next 

menu or 

parameter

Press and hold for three seconds 

to access Adjust Mode

Press to select menu 

or parameter to edit

Press to exit current menu or 

cancel current editing session

Quick Menu and Commands

See separate instruction card 110493-(XX) for these additional advanced menus: 

Password, History, Diagnostic, Firing Rate, Setpoints, Pump, Lead/Lag

When not flashing or alternating, this 

temperature is:

• DHW outlet temperature during DHW priority

• Boiler supply temperature at all other times
Visible when Central Heating demand is 

present
Visible when DHW heating demand is present, 

icon will flash if DHW setpoint is being 

adjusted
Visible when burner is firing, icon adjacent to 

active priority
Visible when Central Heating setpoint reset is 

enabled
Visible when adjust mode is active, icon will 

flash if manual mode is enabled

Visible when manual reset lockout is active

+

A

Quick Menu

Default

a01

Boiler Switch:

 On/Off

On

a02

DHW Comfort Mode: 

On/Off*

Off

a03

DHW Setpoint:

 

(60°F to 140°F, 16°C to 60°C)

120°F

49°C

a04

Central Heat 1 Setpoint:

 

(60°F to 190°F, 16°C to 88°C)

180°F

83°C

a05

Central Heat 2 Setpoint: 

(60°F to 190°F, 16°C to 88°C)

180°F

83°C

*DHW comfort mode not available on heating-only boilers