3
GENERAL
This publication contains Controls, Operation, Start-Up, Ser-
vice and Troubleshooting information for the 30XV140-500
air-cooled liquid chillers with Greenspeed
®
Intelligence and
electronic controls. See Table 1. The 30XV chillers are
equipped with the Carrier Controller controls, electronic ex-
pansion valves, and variable speed fans and compressors.
Table 1 — Unit Sizes
Conventions Used in This Manual
The following conventions for discussing configuration points
for the Carrier Controller display will be used in this manual.
The menu items are shown in this document as they appear on
the Carrier Controller display. A path name for each item will
show the user how to navigate through the Carrier Controller
display to reach the desired configuration. The arrow symbol
(
) in the path name represents touching the menu item on the
screen of the Carrier Controller display. The path will be
shown in bold and italics. See Appendix A for a complete list
of Carrier Controller menu items and descriptions. The Carrier
Comfort Network
®
(CCN) and Building Automation and Con-
trols Network (BACnet)
1
point names are shown in
bold
. See
Appendix B for a list of CCN points, and Appendix D for a list
of BACnet points.
Abbreviations Used in This Manual
The following abbreviations are used in this manual:
*SCT and SDT are used interchangeably by software points.
UNIT
NOMINAL CAPACITY (TONS)
30XV140
140
30XV160
160
30XV180
180
30XV200
200
30XV225
225
30XV250
250
30XV275
275
30XV300
300
30XV325
325
30XV350
350
30XV400
400
30XV450
450
30XV500
500
1. BACnet is a registered trademark of ASHRAE (American Society of
Heating, Refrigerating, and Air-Conditioning Engineers).
ABV
— Actuated Ball Valve
AI
— Analog Input
ANSI
— American National Standards Institute
AO
— Analog Output
ASHRAE
— American Society of Heating, Refrigeration, and Air-Conditioning
Engineers
AUX
— Auxiliary (Board)
AV
— Analog Value
AVM
— Asynchronous Vector Modulation
AWG
— American Wire Gage
BACnet
— Building Automation and Controls Network
BMS
— Building Management System
BUS TER
— Bus Termination
BV
— Binary Value
CB
— Circuit Breaker
CCN
— Carrier Comfort Network
®
CLR HTR
— Cooler Heater
CMD
— Command
COM
— Communications
COV
— Change of Value
CSR
— Current Sensing Relay
CWFS
— Chilled Water Flow Switch
DC
— Direct Current
DGT
— Discharge Gas Temperature
DI
— Digital Input
DNS
— Domain Name Server
DO
— Digital Output
DP
— Discharge Pressure
DPT
— Discharge Pressure Transducer
DSH
— Discharge Superheat
ECM
— Electronically Commutated Motor
ECO EXV
— Economizer Electronic Expansion Valve
ECO
— Economizer
ECT
— Economizer Temperature
EEPROM
— Electronically Erasable Programmable Read-Only Memory
EMM
— Energy Management Module
EOR
— Enable-Off-Remote
EPT
— Economizer Pressure Transducer
EWT
— Entering Water Temperature
EWTO
— Entering Water Temperature Offset
EXV
— Electronic Expansion Valve
FC
— Fan Contactor
FM
— Fan Motor
ft-lb
— Foot-pounds
FTP
— File Transfer Protocol
gal
— Gallon
GLCP
— Graphical Local Control Panel
gpm
— gallons per minute
HMI
— Human Machine Interface
HPS
— High Pressure Switch
HTTP
— Hypertext Transfer Protocol
HVAC
— Heating, Ventilation and Air-Conditioning
Hz
— Hertz
IGBT
— Insultated Gate Bipolar Transistor
in.-lb
— Inch-pounds
IP
— Internet Protocol
IR
— Intrinsic Reporting
kg
— Kilograms
kHz
— Kilohertz
kPa
— Kilopascals
kW
— Kilowatt
L
— Liters
L/s
— Liters per second
lb
— Pounds
LCD
— Liquid Crystal Display
LCP
— Local Control Panel
LED
— Light-Emitting Diode
LEN
— Local Equipment Network
LIQT
— Liquid Temperature
LPT
— Liquid Pressure Transducer
LWT
— Leaving Water Temperature
mA
— Milliamps
MCHX
— Microchannel Heat Exchanger
mm
— Millimeter
MOP
— Maximum operating temperature
N/A
— Not Applicable
N-m
— Newton-Meter
NPT
— National Pipe Thread
OAT
— Outdoor Air Temperature
OP
— Oil Pressure
OPT
— Oil Pressure Transducer
PC
— Personal Computer
ppm
— parts per million
PSI
— Pounds per square inch
Psig
— Pounds per square inch gauge
PTC
— Positive Temperature Coefficient
PVC
— Polyvinyl Chloride
RCD
— Replacement Components Division
RFI
— Radio Frequency Interference
RNET
— Communication Protocol
RO
— Read only
rpm
— revolutions per minute
RTPF
— Round Tube Plate Fin
RW
— Read/Write
SAE
— Society of Automotive Engineers
SCT
— Saturated Condensing Temperature*
SDT
— Saturated Discharge Temperature*
SGT
— Suction Gas Temperature
SHD
— Shield Wire on Shielded Cable
SIOB
— Standard Input/Output Board
SLT
— Saturated Liquid Temperature
SP
— Suction Pressure
Spt
— Setpoint
SPT
— Suction Pressure Transducer
SST
— Saturated Suction Temperature
SSV
— Suction Service Valve
ST
— Space temperature
STPR
— Stepper Motor
SW1
— Switch 1
SW2
— Switch 2
TCP/IP
— Transmission Control Protocol/Internet Protocol
TL
— Trend Log
TS
— Time Schedule
UI
— User Interface
USB
— Universal Serial Bus
USDA
— United States Department of Agriculture
VFD
— Variable Frequency Drive
VI
— Volume Index
VPN
— Virtual Private Network
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...