224
LEGEND
Table 172 — Black Box Function Recorded Parameters
DESCRIPTION
POINT NAME
TEMP_SCT_A
Saturated Condensing Temperature A
TEMP_SCT_B
Saturated Condensing Temperature B
TEMP_SST_A
Saturated Suction Temperature A
TEMP_SST_B
Saturated Suction Temperature B
TEMP_SLT_A
Saturated Liquid Temperature A
TEMP_SLT_B
Saturated Liquid Temperature B
TEMP_SUCT_A
Suction Temperature A
TEMP_SUCT_B
Suction Temperature B
TEMP_DGT_A
Discharge Gas Temperature A
TEMP_DGT_B
Discharge Gas Temperature B
TEMP_LIQ_T_A
Liquid Temperature A
TEMP_LIQ_T_B
Liquid Temperature B
TEMP_CP_TMP_A
Compressor Temperature A
TEMP_CP_TMP_B
Compressor Temperature B
PRESSURE_OP_A
Oil Pressure A
PRESSURE_OP_B
Oil Pressure B
EXV_CTRL_DSH_A
Discharge Superheat A
EXV_CTRL_DSH_B
Discharge Superheat B
TEMP_COOL_EWT
Entering Water Temperature
TEMP_COOL_LWT
Leaving Water Temperature
TEMP_OAT
Outside Air Temperature
GENUNIT_CTRL_PNT
Control Point
EXV_CTRL_EXV_A
EXV Position A
EXV_CTRL_EXV_B
EXV Position B
VLT_DRV_drv_Fa
Compressor VFD Frequency A
VLT_DRV_drv_Fb
Compressor VFD Frequency B
VLT_DRV_drv_Ia
Compressor VFD Current A
VLT_DRV_drv_Ib
Compressor VFD Current B
VLT_DRV_drv_pwra
Compressor VFD Power A
VLT_DRV_drv_pwrb
Compressor VFD Power B
CAPACTRL_cap_pc_a
Capacity Running Circuit A
CAPACTRL_cap_pc_b
Capacity Running Circuit B
CAPACTRL_capmoda
Capacity Control State A
CAPACTRL_capmodb
Capacity Control State B
CAPACTRL_overrida
Capacity Override A
CAPACTRL_overridb
Capacity Override B
EXV_CTRL_exv_sta
EXV State A
EXV_CTRL_exv_stb
EXV State B
EXV_CTRL_ov_exv_a
EXV Override A
EXV_CTRL_ov_exv_b
EXV Overrid B
FAN_DRV_fd_Fa1
Fan VFD Frequency A1
FAN_DRV_fd_Fa2
Fan VFD Frequency A2
FAN_DRV_fd_Fb1
Fan VFD Frequency B1
FAN_DRV_fd_Fb2
Fan VFD Frequency B2
FAN_CTRL_wfan_f_a
Fan Frequency A
FAN_CTRL_wfan_f_b
Fan Frequency B
FAN_CTRL_fan_sta
Fan Control State A
FAN_CTRL_fan_stb
Fan Control State B
GENUNIT_DEM_LIM
Demand Limit
PUMPSTAT_FLOW_SW
Flow Switch 1
PUMPSTAT_FLOW_SWB
Flow Switch 2
OUTPUTS_FCA1
Fan Contactor 1, Circuit A
OUTPUTS_FCA2
Fan Contactor 2, Circuit A
OUTPUTS_FCA3
Fan Contactor 3, Circuit A
OUTPUTS_FCA4
Fan Contactor 4, Circuit A
OUTPUTS_FCA5
Fan Contactor 5, Circuit A
OUTPUTS_FCA6
Fan Contactor 6, Circuit A
OUTPUTS_FCA7
Fan Contactor 7, Circuit A
OUTPUTS_FCA8
Fan Contactor 8, Circuit A
OUTPUTS_FCB1
Fan Contactor 1, Circuit B
OUTPUTS_FCB2
Fan Contactor 2, Circuit B
OUTPUTS_FCB3
Fan Contactor 3, Circuit B
OUTPUTS_FCB4
Fan Contactor 4, Circuit B
OUTPUTS_FCB5
Fan Contactor 5, Circuit B
OUTPUTS_FCB6
Fan Contactor 6, Circuit B
OUTPUTS_FCB7
Fan Contactor 7, Circuit B
OUTPUTS_FCB8
Fan Contactor 8, Circuit B
OUTPUTS_VI_A
VI Solenoid Valve A
OUTPUTS_VI_B
VI Solenoid Valve A
Table 173 — Black Box Function Alarms Collected
ALARM
CODE
ALARM TEXT DESCRIPTION AND CCN MESSAGE
1101
Compressor A Motor temperature too high
1103
Compressor A High Pressure Switch protection
2101
Compressor B Motor temperature too high
2103
Compressor B High Pressure Switch protection
7001
Illegal factory configuration
8001
No factory configuration
10001
Evaporator Freeze Protection
10005
Circuit A Low Suction Temperature
10006
Circuit B Low Suction Temperature
10014
Customer Interlock Failure
10030
Master/Slave communication Failure
10032
Evaporator Pump #1 Fault
10033
Evaporator Pump #2 Fault
10037
Circ A - High condensing temperature out of map compressor
10038
Circ B - High condensing temperature out of map compressor
10050
Refrigerant Leakage Detection
10067
Circuit A Low Oil Pressure
10068
Circuit B Low Oil Pressure
10070
Circuit A Max Oil Filter Differential Pressure
10071
Circuit B Max Oil Filter Differential Pressure
10075
Circuit A Low Oil level
10076
Circuit B Low Oil level
10078
Circuit A High Discharge Gas Temperature
10079
Circuit B High Discharge Gas Temperature
10081
Circuit A Low economizer pressure or suction valve closed
10082
Circuit B Low economizer pressure or suction valve closed
10084
Circuit A High Oil Filter Pressure Drop
10085
Circuit B High Oil Filter Pressure Drop
10087
Circ A - Loss of Refrigerant Flow
10088
Circ B - Loss of Refrigerant Flow
10091
Evaporator Flow Switch Failure
10097
Water Exchanger Temperature Sensors Swapped
10101
Circuit A - saturated suction Temperature out of MAP compressor
10102
Circuit B - saturated suction Temperature out of MAP compressor
17001
Circuit A Compressor VFD Failure
18001
Circuit B Compressor VFD Failure
20001
Circuit A Fan VFD 1 Failure
21001
Circuit A Fan VFD 2 Failure
22001
Circuit A Fan VFD 3 Failure
23001
Circuit B Fan VFD 1 Failure
24001
Circuit B Fan VFD 2 Failure
25001
Circuit B Fan VFD 3 Failure
35001
Circuit A Compressor VFD Warning
36001
Circuit B Compressor VFD Warning
38001
Circuit A Fan VFD 1 Warning
39001
Circuit A Fan VFD 2 Warning
40001
Circuit A Fan VFD 3 Warning
41001
Circuit B Fan VFD 1 Warning
42001
Circuit B Fan VFD 2 Warning
43001
Circuit B Fan VFD 3 Warning
55001
Database module Failure
56001
Lenscan module Failure
57020
Main EXV stepper motor Failure - cir A
57021
Main EXV stepper motor Failure - cir B
57023
EXV eco stepper motor Failure - cir A
57024
EXV eco stepper motor Failure - cir B
60001
VI Solenoid Diagnostic Test Failure - cir A
61001
VI Solenoid Diagnostic Test Failure - cir B
A
—
Circuit A
B
—
Circuit B
EXV
—
Electronic Expansion Valve
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...