29
number must be changed to configure the unit to broadcast a
Global Time Schedule. The Schedule Number can be set from
65 to 99 (OCCPC65S to OCCPC99S). When OCC1PxxS is set
to a value of 65 or greater and all attached schedules are 00:00
(that is, no occupied time periods), an occupancy flag is broad-
cast over the CCN every time it transitions from occupied to
unoccupied or vice-versa. The ComfortVIEW™ Network
Manager’s Configure and Modify commands or the Service
Tool’s Modify/Names function must be used to change the
number of the Occupancy Equipment Part Table Name (OC-
CPC01E) to the Global Schedule Number. The Schedule Num-
ber can be set from 65 to 99 (OCCPC65E to OCCPC99E).
Table 23 — Active Cooling Set Point Parameters
* Ice Storage Configuration and Ice Done Contact apply only to units
with EMM.
OPERATING
TYPE
PARAMETER STATUS
ACTIVE SETPOINT
Setpoint
Selection
Ice Storage
Configuration*
Ice Done
Contact*
Setpoint
Switch
Schedule 2 Status
Local
sp-1
Default
Any
Any
Default
Cooling Setpoint 1
sp-2
No
Any
Any
Default
Cooling Setpoint 2
sp-2
Yes
Closed
Any
N/A
Cooling Setpoint 2
sp-2
Yes
Open
Any
N/A
Cooling Ice Setpoint
automatic
Default
Any
Any
Occupied
Cooling Setpoint 1
automatic
No
Any
Any
Unoccupied
Cooling Setpoint 2
automatic
Yes
Closed
Any
Unoccupied
Cooling Setpoint 2
automatic
Yes
Open
Any
Unoccupied
Cooling Ice Setpoint
Remote
Default
Default
Any
Open
Default
Cooling Setpoint 1
Default
No
Any
Closed
Default
Cooling Setpoint 2
N/A
Yes
Closed
Closed
N/A
Cooling Setpoint 2
Default
Yes
Open
Closed
Default
Cooling Ice Setpoint
Network
Default
Default
Any
Any
Occupied
Cooling Setpoint 1
Default
Default
Any
Any
Unoccupied
Cooling Setpoint 2
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...