APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Configuration/PUMPCONF
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Evap Pumps Sequence
0 = No Pump
1 = One Pump Only
2 = Two Pumps Auto
3 = Pump#1 Manual
4 = Pump#2 Manual
cpumpseq
N
N/A
Pump Auto Rotation Delay
Range: 24-3000
Default: 48
hours
pump_del
N
N/A
N
N/A
Pump Sticking Protection
No/Yes
pump_per
N
N/A
Flow Checked If Pump Off
No/Yes
pump_loc
N
N/A
Configuration/RESETCFG
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Cooling Reset Select
0=None
1=OAT
2=Delta T
3=4 to 20mA control
4=Space Temp
cr_sel
N
N/A
Cooling
N
N/A
OAT No Reset Value
°F (°C)
oat_crno
N
N/A
OAT Full Reset Value
°F (°C)
oat_crfu
N
N/A
Delta T No Reset Value
°F (°C)
dt_cr_no
N
N/A
Delta T Full Reset Value
°F (°C)
dt_cr_fu
N
N/A
Current No Reset Value
mA
v_cr_no
N
N/A
Current Full Reset Value
mA
v_cr_fu
N
N/A
Space T No Reset Value
°F (°C)
spacr_no
N
N/A
Space T Full Reset Value
°F (°C)
spacr_fu
N
N/A
Cooling Reset Deg. Value
°F (°C)
cr_deg
N
N/A
Configuration/USER
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
User Password
11=User
use_pass
N
N/A
Service\BACNET
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
BACnet Enable
Disabel/Enable
bacena
N
N/A
Metric Unit
No/Yes
bacunit
N
N/A
Network
Range: 1 to 9999
Default: 1601
network
N
N/A
Identifier
Range: 0 to 9999999
Default: 1600001
ident
N
N/A
BACnet Management Device
0=None
1=FD(Foreign Device)
2=BBMD(BACnet Broadcast
Management Device)
bbmd
N
N/A
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...