APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Maintenance\TBLSHT - Troubleshoot (cont)
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Motor Temperature Cir A
°F (°C)
CP_TMP_A
Y
RO
EXV Eco. Tmp Cir A
°F (°C)
ECO_T_A
Y
RO
Discharge Superheat A
°F (°C)
DSH_A
Y
RO
Suction Superheat A
°F (°C)
SH_A
Y
RO
Liquid Temperature A
°F (°C)
LIQ_T_A
Y
RO
Discharge Pressure A
PSI (Kpa)
DP_A
Y
RO
Main Suction Pressure A
PSI (Kpa)
SP_A
Y
RO
Oil Pressure A
PSI (Kpa)
OP_A
Y
RO
Oil Pressure DifferenceA
PSI (Kpa)
DOP_A
Y
RO
Oil Level Input A
Off/On
OIL_L_A
Y
RO
Oil Solenoid Output A
Off/On
OIL_SL_A
Y
RO
Economizer Pressure A
PSI (Kpa)
ECO_P_A
Y
RO
Liquid Pressure A
PSI (Kpa)
LIQ_P_A
Y
RO
Capacity Signal Cir B
Volts
CAPT010B
Y
RO
Cir B Drive Amps
AMPS
drv_Ib
N
N/A
Cir B Drive Speed
rpm
drv_Sb
N
N/A
Saturated Cond Tmp Cir B
°F (°C)
SCT_B
Y
RO
Saturated Suction Temp B
°F (°C)
SST_B
Y
RO
Saturated Liquid Temp B
°F (°C)
SLT_B
Y
RO
Compressor Suction Tmp B
°F (°C)
SUCT_B
Y
RO
Discharge Gas Temp Cir B
°F (°C)
DGT_B
Y
RO
Motor Temperature Cir B
°F (°C)
CP_TMP_B
Y
RO
EXV Eco. Tmp Cir B
°F (°C)
ECO_T_B
Y
RO
Discharge Superheat B
°F (°C)
DSH_B
Y
RO
Suction Superheat B
°F (°C)
SH_B
Y
RO
Liquid Temperature B
°F (°C)
LIQ_T_B
Y
RO
Discharge Pressure B
PSI (Kpa)
DP_B
Y
RO
Main Suction Pressure B
PSI (Kpa)
SP_B
Y
RO
Oil Pressure B
PSI (Kpa)
OP_B
Y
RO
Oil Pressure DifferenceB
PSI (Kpa)
DOP_B
Y
RO
Oil Level Input B
Off/On
OIL_L_B
Y
RO
Oil Solenoid Output B
Off/On
OIL_SL_B
Y
RO
Economizer Pressure B
PSI (Kpa)
ECO_P_B
Y
RO
Liquid Pressure B
PSI (Kpa)
LIQ_P_B
Y
RO
Comm with Cmp VFD A Ok
-
VLT_COMA
Y
N/A
Comm with Cmp VFD B Ok
-
VLT_COMB
Y
N/A
Comm with Fan VFD A1 Ok
-
FD_COMA1
Y
RO
Comm with Fan VFD A2 Ok
-
FD_COMA2
Y
RO
Comm with Fan VFD A3 Ok
-
FD_COMA3
Y
RO
Comm with Fan VFD B1 Ok
-
FD_COMB1
Y
RO
Comm with Fan VFD B2 Ok
-
FD_COMB2
Y
RO
Comm with Fan VFD B3 Ok
-
FD_COMB3
Y
RO
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...