![Carrier AquaForce 30XV140 Controls, Start-Up, Operation, Service And Troubleshooting Instructions Download Page 282](http://html1.mh-extra.com/html/carrier/aquaforce-30xv140/aquaforce-30xv140_controls-start-up-operation-service-and-troubleshooting-instructions_2562366282.webp)
282
APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Status/MODES - Modes
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Start Up Delay In Effect
No/Yes
m_delay
N
N/A
Second Setpoint In Use
No/Yes
m_2stpt
N
N/A
Reset In Effect
No/Yes
m_reset
N
N/A
Demand Limit Active
No/Yes
m_demlim
N
N/A
Evaporator Pump Rotation
No/Yes
m_pmprot
N
N/A
Pump Periodic Start
No/Yes
m_pmpper
N
N/A
Night Low Noise Active
No/Yes
m_night
N
N/A
Master Slave Active No/Yes
m_slave
N
N/A
Ice Mode In Effect
No/Yes
m_ice
N
N/A
Current Alarm 1
Current Alarm 1
-
m_alarm1
N
N/A
Current Alarm 2
Current Alarm 2
-
m_alarm2
N
N/A
Current Alarm 3
Current Alarm 3
-
m_alarm3
N
N/A
Current Alarm 4
Current Alarm 4
-
m_alarm4
N
N/A
Current Alarm 5
Current Alarm 5
-
m_alarm5
N
N/A
Status/OUTPUTS - Outputs Status
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
CIRCUIT A
Normal/Alarm
LABEL_A
Y
N/A
Compressor A
Off/On
CP_A
Y
RO
Oil Solenoid Output A
Off/On
OIL_SL_A
Y
RO
VI Solenoid Output A
Off/On
VI_A
Y
RO
Capacity Signal Cir A
0 to 10
Volts
CAPT010A
Y
RO
VariFan Speed A
0 to 100
%
VFAN_A
Y
RO
Ref Iso Relay Energize A
Off/On
ISO_OP_A
Y
RO
Ref Iso Valve State A
Close/Open
ISO_POSA
Y
RO
Oil Heater Output A
Off/On
OIL_HT_A
Y
RO
CIRCUIT B
Normal/Alarm
LABEL_B
Y
N/A
Capacity Signal Cir B
0 to 10
Volts
CAPT010B
Y
RO
VariFan Speed B
0 to 100
%
VFAN_B
Y
RO
Compressor B
Off/On
CP_B
Y
RO
Oil Solenoid Output B
Off/On
OIL_SL_B
Y
RO
VI Solenoid Output B
Off/On
VI_B
Y
RO
Ref Iso Relay Energize B
Off/On
ISO_OP_B
Y
RO
Ref Iso Valve State B
Close/Open
ISO_POSB
Y
RO
Oil Heater Output B
Off/On
OIL_HT_B
Y
RO
Alarm Relay Status
Off/On
ALARM
Y
RO
Running Relay Status Off/On
RUNNING
Y
RO
Chiller Capacity Signal
0 to 10
Volts
CAPT_010
Y
RO
Alert Relay State
Off/On
ALERT
Y
RO
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...