APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
*Depends on the selected language (English by default).
EXV_CTRL — EXV Control
Carrier Controller PATH:
Main Menu
Maintenance Menu
EXV Control
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
Circuit A
—
—
—
—
—
2
EXV Override Circuit A
ov_exv_a
—
—
—
RO
3
EXV Position (Pct) A
EXV_A
—
—
%
RO
4
EXV Position (Steps) A
EXV_STPA
0 to 10000
—
—
RO
5
Discharge Superheat A
DSH_A
—
—
°F (°C)
RO
6
Dis. Superheat Setpnt A
dsh_spa
—
—
°F (°C)
RO
7
Suction Superheat A
SH_A
—
—
°F (°C)
RO
8
Suct. Superheat Setpnt A
sh_sp_a
—
—
°F (°C)
RO
9
Evap ExchangeDT Cir A
pinch_a
—
—
°F (°C)
RO
10
Subcooling Circuit A
subcoola
—
—
°F (°C)
RO
11
Subcooling Setpoint A
subc_spa
—
—
°F (°C)
RO
12
EXV State A
exv_sta
—
—
—
RO
13
EXV Previous State A
exv_lsta
—
—
—
RO
14
EXV Wished Position A
exvwposa
—
—
—
RO
15
EXV Mode A
exv_moda
Closed(0)/Open(1)
—
—
RO
16
EXV Mode Text A
exv_txta
Closed(0)/Open(1)
—
—
RO
17
Circuit B
—
—
—
—
—
18
EXV Override Circuit B
ov_exv_b
—
—
—
RO
19
EXV Position (Pct) B
EXV_B
—
—
%
RO
20
EXV Position (Steps) B
EXV_STPB
0 to 10000
—
—
RO
21
Discharge Superheat B
DSH_B
—
—
°F (°C)
RO
22
Dis. Superheat Setpnt B
dsh_spb
—
—
°F (°C)
RO
23
Suction Superheat B
SH_B
—
—
°F (°C)
RO
24
Suct. Superheat Setpnt B
sh_sp_b
—
—
°F (°C)
RO
25
Evap ExchangeDT Cir B
pinch_b
—
—
°F (°C)
RO
26
Subcooling Circuit B
subcoolb
—
—
°F (°C)
RO
27
Subcooling Setpoint B
subc_spb
—
—
°F (°C)
RO
28
EXV State B
exv_stb
—
—
—
RO
29
EXV Previous State B
exv_lstb
—
—
—
RO
30
EXV Wished Position B
exvwposb
—
—
—
RO
31
EXV Mode B
exv_modb
Closed(0)/Open(1)
—
—
RO
32
EXV Mode Text B
exv_txtb
Closed(0)/Open(1)
—
—
RO
LEGEND
RO
—
Read Only
RW
—
Read/Write
Spt
—
Set Point
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...