APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
*
Depends on the selected language (English by default).
LEGEND
*
Depends on the selected language (English by default).
PUMPSTAT — Pump Status
Carrier Controller PATH: Main Menu
Pump Status
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
Evap Pump #1 Command
CPUMP_1
Off(0)/On(1)
Off(0)
—
RW
2
Evap Pump #2 Command
CPUMP_2
Off(0)/On(1)
Off(0)
—
RW
3
Rotate Evap Pumps ?
ROTCPUMP
No(0)/Yes(1)
No(0)
—
RW
4
Evap Flow Switch #1
FLOW_SW
Open(0)/Close(1)
—
—
RO
5
Evap Flow Switch #2
FLOW_SWB
Open(0)/Close(1)
—
—
RO
6
Countdown to Rotate
ROTCNTDN
0 to 0
0
hours
RO
RUNTIME — Run Times
Carrier Controller PATH: Main Menu
Run Times
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
Machine Operating Hours
HR_MACH
—
—
hours
RO
2
Machine Starts
st_mach
—
—
—
RO
3
Compressor A Hours
HR_CP_A
—
—
hours
RO
4
Compressor A Starts
st_cp_a
—
—
—
RO
5
Compressor B Hours
HR_CP_B
—
—
hours
RO
6
Compressor B Starts
st_cp_b
—
—
—
RO
7
Evap Pump #1 Hours
hr_cpum1
—
—
hours
RO
8
Evap Pump #2 Hours
hr_cpum2
—
—
hours
RO
9
VI Cycle Count A
VIctA
—
—
cycles
RO
10
VI Cycle Count B
VIctB
—
—
cycles
RO
11
Circuit A Fan #1 Hours
hrfana01
—
—
hours
RO
12
Circuit A Fan #2 Hours
hrfana02
—
—
hours
RO
13
Circuit A Fan #3 Hours
hrfana03
—
—
hours
RO
14
Circuit A Fan #4 Hours
hrfana04
—
—
hours
RO
15
Circuit A Fan #5 Hours
hrfana05
—
—
hours
RO
16
Circuit A Fan #6 Hours
hrfana06
—
—
hours
RO
17
Circuit A Fan #7 Hours
hrfana07
—
—
hours
RO
18
Circuit A Fan #8 Hours
hrfana08
—
—
hours
RO
19
Circuit A Fan #9 Hours
hrfana09
—
—
hours
RO
20
Circuit A Fan #10 Hours
hrfana10
—
—
hours
RO
21
Circuit A Fan #11 Hours
hrfana11
—
—
hours
RO
22
Circuit A Fan #12 Hours
hrfana12
—
—
hours
RO
23
Circuit A Fan #13 Hours
hrfana13
—
—
hours
RO
24
Circuit A Fan #14 Hours
hrfana14
—
—
hours
RO
25
Circuit B Fan #1 Hours
hrfanb01
—
—
hours
RO
26
Circuit B Fan #2 Hours
hrfanb02
—
—
hours
RO
27
Circuit B Fan #3 Hours
hrfanb03
—
—
hours
RO
28
Circuit B Fan #4 Hours
hrfanb04
—
—
hours
RO
29
Circuit B Fan #5 Hours
hrfanb05
—
—
hours
RO
30
Circuit B Fan #6 Hours
hrfanb06
—
—
hours
RO
31
Circuit B Fan #7 Hours
hrfanb07
—
—
hours
RO
32
Circuit B Fan #8 Hours
hrfanb08
—
—
hours
RO
33
Circuit B Fan #9 Hours
hrfanb09
—
—
hours
RO
34
Circuit B Fan #10 Hours
hrfanb10
—
—
hours
RO
35
Circuit B Fan #11 Hours
hrfanb11
—
—
hours
RO
36
Circuit B Fan #12 Hours
hrfanb12
—
—
hours
RO
37
Circuit B Fan #13 Hours
hrfanb13
—
—
hours
RO
38
Circuit B Fan #14 Hours
hrfanb14
—
—
hours
RO
RO —
Read Only
RW —
Read/Write
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...