APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Service\SERVICE1 (cont)
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Send comp. drive config?
No/Yes
cdrv_cfg
N
N/A
Evap Heater Delta Spt
Range: 0 to 6
Default: 2
heatersp
N
N/A
Freeze Override Offset
Range: 0 to 5.8
Default: 0
°F (°C)
freez_ov
N
N/A
Auto Start When SM Lost
Disable/Enable
auto_sm
N
N/A
VI Self-Test Threshold
Range: 0.5 to 15
Default: 1.15
kW
ViPwrChk
N
N/A
VI Self-Test Enable
Off/On
ViChkEn
N
N/A
Pump Rot. AntiFrz Protec
Off/On
AntiFrz
N
N/A
HTTP Server
Disable/Enable
http_en
N
N/A
FTP Server
Disable/Enable
ftp_en
N
N/A
Oil Delta Trigger Speed
Range: 0 to 15
Default: 5
Hz
odtrspd
N
N/A
Oil Trigger Time
Range: 1800 to 7200
Default: 3600
sec
otrigtim
N
N/A
Oil Delta Recover Speed
Range: 0 to 15
Default: 5
Hz
odrecspd
N
N/A
Oil Recover Time
Range: 30 to 120
Default: 60
sec
orectim
N
N/A
Water Temp Hysteresis
0.9 to 10
Default: 0.9
V
wateesys
N
N/A
High VI Time at Start
0 to 3600
Default: 900
TONS/H
vistrtdt
N
N/A
Enable High VI at Start
NO_YES
TONS/H
vistrten
N
N/A
Approach Ctrl at Start?
NO_YES
A
apr_en
N
N/A
Service\UPDTHOUR
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Machine Operating Hours
hours
hr_mach
N
N/A
Machine Starts Number
st_mach
N
N/A
Compressor A Hours
hours
hr_cp_a
N
N/A
Compressor A Starts
st_cp_a
N
N/A
Compressor B Hours
hours
hr_cp_b
N
N/A
Compressor B Starts
st_cp_b
N
N/A
Evap Pump #1 Hours
hours
hr_cpum1
N
N/A
Evap Pump #2 Hours
hours
hr_cpum2
N
N/A
VI Cycle Count A
Cycles
VIctA
N
N/A
VI Cycle Count B
Cycles
VIctB
N
N/A
Circuit A Fan #1 Hours
hours
hrfana01
N
N/A
Circuit A Fan #2 Hours
hours
hrfana02
N
N/A
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...