APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
*
Depends on the selected language (English by default).
† Points are RO unless the Configure Bar is selected at which time ALL
the points become RW.
NET_ETH0 — Network Conn-eth0
Carrier Controller PATH: Main Menu
Configuration Menu
HMI Configuration
Network Conn-eth0
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE†
1
MAC address
RO
2
IP address
RO
3
Subnet Mask
RO
4
Default Gateway
RO
5
DNS Server1
RO
6
DNS Server2
RO
NET_ETH1 — Network Conn-eth1
Carrier Controller PATH: Main Menu
Configuration Menu
HMI Configuration
Network Conn-eth1
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE†
1
MAC address
RO
2
IP address
RO
3
Subnet Mask
RO
4
Default Gateway
RO
5
DNS Server1
RO
6
DNS Server2
RO
CCN_CONF — CCN Configuration
Carrier Controller PATH: Main Menu
Configuration Menu
HMI Configuration
CCN Configuration
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE†
1
CCN address
1
RW
2
CCN Bus
0
RW
3
Primary Bus Baud Rate
9600
19200
38400
9600
RW
BACCONF — BACNet Standard Configuration
Carrier Controller PATH: Main Menu
Configuration Menu
HMI Configuration
BACNet Configuration
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE†
—
BACnet Enable
bacena
Disable(0)/
Enable(1)
Enable(1)
—
—
1
Metric Units
bacunit
No(0)/Yes(1)
Yes(1)
—
RW
2
Network
network
1 to 9999
1601
—
RW
3
Identifier
ident
0 to 9999999
1610101
—
RW
4
BACnet Mgmt Device†
bbmd
0 to 2
0
—
RW
5
BACnet Data Link Layer
XXXXX
MS/TP(0)/
BACnet IP(1)
XXXXX
—
RW
6
MS/TP MAC Address
XXXXX
XXXXX
XXXXX
—
RW
7
MS/TP Baud Rate
XXXXX
XXXXX
XXXXX
—
RW
8
Max Masters
XXXXX
XXXXX
XXXXX
—
RW
9
MS/TP Max Info Frames
XXXXX
XXXXX
XXXXX
—
RW
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...