116
Table 76 — VFD Parameters, St Tier, for 460 V/60 Hz Units, 30XV160-200
NOTE: Compressor motor voltage is 380V.
PARAMETER
SETTING
DESCRIPTION
30XV160
30XV180
30XV200
COMP
FAN
COMP
FAN
COMP
FAN
NUMBER DESCRIPTION
A
B
A1
A2
B1
B2
A
B
A1
A2
B1
B2
A
B
A1
A2
B1
B2
0-40
hand on
button
disabled
0
0
N/A
—
N/A
—
0
0
N/A
—
N/A
—
0
0
N/A
—
N/A
—
1-03
torque profile
Compressor
Torque
0
0
N/A
—
N/A
—
0
0
N/A
—
N/A
—
0
0
N/A
—
N/A
—
1-20
motor kW
size
dependent
97
97
9.2
—
9.2
—
97
97
9.2
—
9.2
—
97
97
11.5
—
11.5
—
1-22
motor volts
motor
dependent
460
460
460
—
460
—
460
460
460
—
460
—
460
460
460
—
460
—
1-23
motor
frequency
motor
dependent
105
105
60
—
60
—
105
105
60
—
60
—
105
105
60
—
60
—
1-24
motor
amperage
size
dependent
168
168
17.6
—
17.6
—
197
197
17.6
—
17.6
—
200
200
22
—
22
—
1-25
motor rpm
size
dependent
6240 6240 1130
—
1130
—
6240 6240 1130
—
1130
—
6240 6240 1130
—
1130
—
1-71
compressor
start delay
0s
0
0
N/A
—
N/A
—
0
0
N/A
—
N/A
—
0
0
N/A
—
N/A
—
1-73
Flying Restart
NO
N/A
N/A
0
—
0
—
N/A
N/A
0
—
0
—
N/A
N/A
0
—
0
—
1-78
starting
frequency
26hz
26
26
N/A
—
N/A
—
26
26
N/A
—
N/A
—
26
26
N/A
—
N/A
—
1-79
Comp start
maxtime to
trip
5s
5
5
N/A
—
N/A
—
5
5
N/A
—
N/A
—
5
5
N/A
—
N/A
—
1-80
function at
stop
coast
0
0
0
—
0
—
0
0
0
—
0
—
0
0
0
—
0
—
1-90
motor ther-
mal protection
0
0
0
0
—
0
—
0
0
0
—
0
—
0
0
0
—
0
—
3-02
min ref
0
0
0
N/A
—
N/A
—
0
0
N/A
—
N/A
—
0
0
N/A
—
N/A
—
3-03
max reference
size
dependent
85
85
60
—
60
—
95
95
60
—
60
—
105
105
60
—
60
—
3-13
type reference
remote
1
1
0
—
0
—
1
1
0
—
0
—
1
1
0
—
0
—
3-15
src ref#1
no function
0
0
0
—
0
—
0
0
0
—
0
—
0
0
0
—
0
—
3-16
src ref#2
no function
0
0
0
—
0
—
0
0
0
—
0
—
0
0
0
—
0
—
3-41
ramp up
100s
100
100
20
—
20
—
100
100
20
—
20
—
100
100
20
—
20
—
3-42
ramp down
100s
100
100
20
—
20
—
100
100
20
—
20
—
100
100
20
—
20
—
3-82
starting ramp
time
3s
3
3
N/A
—
N/A
—
3
3
N/A
—
N/A
—
3
3
N/A
—
N/A
—
4-10
motor speed
direct
clockwise
0
0
0
—
0
—
0
0
0
—
0
—
0
0
0
—
0
—
4-12
motor speed
low limit
26Hz
26
26
5
—
5
—
26
26
5
—
5
—
26
26
5
—
5
—
4-14
motor speed
high limit
95Hz
85
85
60
—
60
—
95
95
60
—
60
—
105
105
60
—
60
—
4-16
torque limit
size
dependent
150
150
150
—
150
—
150
150
150
—
150
—
150
150
150
—
150
—
4-18
current limit
size
dependent
110
110
110
—
110
—
110
110
110
—
110
—
110
110
110
—
110
—
4-19
max output
frequency
size
dependent
86
86
N/A
—
N/A
—
96
96
N/A
—
N/A
—
106
106
N/A
—
N/A
—
5-12
DI #27
Coast Inverse
2
2
0
—
0
—
2
2
0
—
0
—
2
2
0
—
0
—
5-19
DI#37 safe
stop
safe stop
alarm
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
5-40[36]
relay 1
control word
bit 11
36
36
N/A
—
N/A
—
36
36
N/A
—
N/A
—
36
36
N/A
—
N/A
—
5-40[5]
relay 2
running
5
5
N/A
—
N/A
—
5
5
N/A
—
N/A
—
5
5
N/A
—
N/A
—
8-01
control site
digital & con-
trol word
0
0
0
—
0
—
0
0
0
—
0
—
0
0
0
—
0
—
8-02
control
source
FC
port=RS485
1
1
1
—
1
—
1
1
1
—
1
—
1
1
1
—
1
—
8-03
time out time
10s
10
10
10
—
10
—
10
10
10
—
10
—
10
10
10
—
10
—
8-04
time out func-
tion
stop and trip
5
5
2
—
2
—
5
5
2
—
2
—
5
5
2
—
2
—
14-00
Pattern [AVM]
60AVM
N/A
N/A
0
—
0
—
N/A
N/A
0
—
0
—
N/A
N/A
0
—
0
—
14-01
switching
frequency
3kHz
4
4
6
—
6
—
4
4
6
—
6
—
4
4
6
—
6
—
14-03
over-
modulation
yes
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
14-10
main failure
alarm
6
6
N/A
—
N/A
—
6
6
N/A
—
N/A
—
6
6
N/A
—
N/A
—
14-11
Mains voltage
at Mains fault
345V
345
345
N/A
—
N/A
—
345
345
N/A
—
N/A
—
345
345
N/A
—
N/A
—
14-50
RFI Filter
on
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
14-60
function at
overtemp
derate
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
14-61
inverter
overload
derate
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
1
1
N/A
—
N/A
—
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...