APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
*Depends on the selected language (English by default).
CAPACTRL — Capacity Control
Carrier Controller PATH:
Main Menu
Maintenance Menu
Capacity Control
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
Controlled Water Temp
ctrl_wt
—
—
°F (°C)
RO
2
Ctrl Water Temp, Deg/Min
cwt_rate
—
—
°F (°C)
RO
3
Current Capacity Limit
cap_lim
0 to 100
100
%
RO
4
Wished Comp. Frequency A
drvcmda
—
—
Hz
RO
5
Capa Ctrl State A
capstata
—
—
—
RO
6
Capa Ctrl State Text A
captxta
—
—
—
RO
7
Override State A
ovrstata
—
—
—
RO
8
Override State Text A
ovrtxta
—
—
—
RO
9
Capa Ctrl Stat Nb A
capmoda
—
—
—
RO
10
Last Capa Ctrl Stat Nb A
lcapmoda
—
—
—
RO
11
Override Capacity Nb A
overrida
—
—
—
RO
12
Estimated Capacity A
cap_pc_a
0 to 100
—
%
RO
13
Wished Comp. Frequency B
drvcmdb
—
—
Hz
RO
14
Capa Ctrl State B
capstatb
—
—
—
RO
15
Capa Ctrl State Text B
captxtb
—
—
—
RO
16
Override State B
ovrstatb
—
—
—
RO
17
Override State Text B
ovrtxtb
—
—
—
RO
18
Capacity Ctrl Stat Nb B
capmodb
—
—
—
RO
19
Last Capa Ctrl Stat Nb B
lcapmodb
—
—
—
RO
20
Override Capacity Nb B
overridb
—
—
—
RO
21
Estimated Capacity B
cap_pc_b
0 to 100
—
%
RO
22
Max Comp. Frequency A
cMaxFrqA
—
95
Hz
RO
23
Max Comp. Frequency B
cMaxFrqB
—
95
Hz
RO
24
Comp. VI Cmd A
viCmdA
—
—
—
RO
25
Comp. VI Cmd B
viCmdB
—
—
—
RO
26
Reset Amount
reset
—
—
°F (°C)
RO
27
Circuit Running Number
CirRunNb
—
—
—
RO
28
State of Circuit A
StatCirA
—
—
—
RO
29
State of Circuit B
StatCirB
—
—
—
RO
30
Dual Circuit Master
DualMast
—
—
—
RO
31
Transfer Spd, add cir
xSpdHigh
0 to 0
60
Hz
RO
32
Transfer Spd, remove cir
xSpdLow
0 to 0
30
Hz
RW
33
Compressor Start Freq
cStrtFrq
0 to 0
26
Hz
RO
34
Compressor Min Frequency
cMinFrq
0 to 0
26
Hz
RO
35
DGT A, Deg/min
dgt_dt_a
—
—
°F (°C)
RO
36
SST A, Deg/min
sst_dt_a
—
—
°F (°C)
RO
37
DGT B, Deg/min
dgt_dt_b
—
—
°F (°C)
RO
38
SST B, Deg/min
sst_dt_b
—
—
°F (°C)
RO
LEGEND
RO
—
Read Only
RW
—
Read/Write
Spt
—
Set Point
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...