305
APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Service\MST_SLV
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
MASTER/SLAVE CONTROL
Master/Slave Select
0=disable
1=Master
2=Slave
ms_sel
N
N/A
Master Control Type
1=Local Control
2=Remote Control
3=CCN Control
ms_ctrl
N
N/A
Slave Address
slv_addr
N
N/A
Lead Lag Select
0=Always Lead
1=Lag Once Failed Only
2=Lead/Lag Runtime Sel
lead_sel
N
N/A
Lead/Lag Balance Delta
hours
ll_bal_d
N
N/A
Lead/Lag Start Timer
min
lstr_tim
N
N/A
Lead Pulldown Time
min
lead_pul
N
N/A
Start If Error Higher
°F (°C)
start_dt
N
N/A
Lag Minimum Running Time
min
lag_mini
N
N/A
Lag Unit Pump Control
0=Stop if Unit Stops
1=Run if unit Stops
lag_pump
N
N/A
Chiller In Series
No/Yes
ll_serie
N
N/A
Service\SERVICE1
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Evaporator Fluid Type
1 = Water
2 = Med Brine
3=Low Brine
flui_typ
N
N/A
Entering Fluid Control
No/Yes
ewt_opt
N
N/A
Brine Freeze Setpoint
Range: -20 to 34
Default: 34
°F (°C)
freezesp
N
N/A
Brine Minimum Fluid Temp
Range: -20 to 38
Default: 38
°F (°C)
mini_lwt
N
N/A
Fast Capacity Recovery
0=Disabled
1=Quickstart Load
2=Fast Capacity Recovery
fastcapr
N
N/A
EWT Probe on Cir A Side
No/Yes
ewt_cirA
N
N/A
Service Password
Range: 0 to 9999
Default: 88
ser_pass
N
N/A
Leakage Charge Threshold
Range: 0 to 10
Default: 2.5
Volts
leak_thr
N
N/A
Leakage Charge Timer
Range: 0 to 600
Default: 60
min
leak_tmr
N
N/A
Compressor RFI Filter En
Off/On
RFI_conf
N
N/A
Metric Units? (Blackbox)
No/Yes
metric
N
N/A
Send fan drive config?
No/Yes
fdrv_cfg
N
N/A
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...