105
Table 65 — VFD Parameters, Standard Tier, for 575 V/60 Hz Units, 30XV250-325
NOTE: Compressor motor voltage is 460V.
PARAMETER
NUMBER
PARAMETER
DESCRIPTION
SETTING
DESCRIPTION
30XV250
30XV275
30XV300
30XV325
COMPRESSOR
COMPRESSOR
COMPRESSOR
COMPRESSOR
A
B
A
B
A
B
A
B
0-40
hand on button
disabled
0
0
0
0
0
0
0
0
1-03
torque profile
Compressor Torque
0
0
0
0
0
0
0
0
1-20
motor kW
size dependent
160
160
160
160
160
160
160
160
1-22
motor volts
motor dependent
460
460
460
460
460
460
460
460
1-23
motor frequency
motor dependent
98
98
98
98
98
98
98
98
1-24
motor amperage
size dependent
273
273
296
296
302
302
330
330
1-25
motor rpm
size dependent
5830
5830
5830
5830
5830
5830
5830
5830
1-71
compressor start delay
0s
0
0
0
0
0
0
0
0
1-78
starting frequency
26hz
26
26
26
26
26
26
26
26
1-79
Comp start max time to trip
5s
5
5
5
5
5
5
5
5
1-80
function at stop
coast
0
0
0
0
0
0
0
0
1-90
motor thermal protection
0
0
0
0
0
0
0
0
0
3-02
min ref
0
0
0
0
0
0
0
0
0
3-03
max reference
size dependent
80
80
85
85
90
90
98
98
3-13
type reference
remote
1
1
1
1
1
1
1
1
3-15
src ref#1
no function
0
0
0
0
0
0
0
0
3-16
src ref#2
no function
0
0
0
0
0
0
0
0
3-41
ramp up
100s
100
100
100
100
100
100
100
100
3-42
ramp down
100s
100
100
100
100
100
100
100
100
3-82
starting ramp time
3s
3
3
3
3
3
3
3
3
4-10
motor speed direct
clockwise
0
0
0
0
0
0
0
0
4-12
motor speed low limit
26Hz
26
26
26
26
26
26
26
26
4-14
motor speed high limit
95Hz
80
80
85
85
90
90
98
98
4-16
torque limit
size dependent
150
150
150
150
150
150
150
150
4-18
current limit
size dependent
110
110
110
110
110
110
110
110
4-19
max output frequency
size dependent
81
81
86
86
91
91
99
99
5-12
DI #27
Coast Inverse
2
2
2
2
2
2
2
2
5-19
DI#37 safe stop
safe stop alarm
1
1
1
1
1
1
1
1
5-40[36]
relay 1
control word bit 11
36
36
36
36
36
36
36
36
5-40[5]
relay 2
running
5
5
5
5
5
5
5
5
8-01
control site
digital & control word
0
0
0
0
0
0
0
0
8-02
control source
FC port=RS485
1
1
1
1
1
1
1
1
8-03
time out time
10s
10
10
10
10
10
10
10
10
8-04
time out function
stop and trip
5
5
5
5
5
5
5
5
14-01
switching frequency
3kHz
4
4
4
4
4
4
4
4
14-03
overmodulation
yes
1
1
1
1
1
1
1
1
14-10
main failure
alarm
6
6
6
6
6
6
6
6
14-11
Mains voltage at Mains fault
345V
489
489
489
489
489
489
489
489
14-50
RFI Filter
on
1
1
1
1
1
1
1
1
14-60
function at overtemp
derate
1
1
1
1
1
1
1
1
14-61
inverter overload
derate
1
1
1
1
1
1
1
1
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...