APPENDIX E — BACNET IP POINTS (cont)
LEGEND
OBJECT NAME
OBJECT TYPE
INSTANCE
OPTION
PV ACCESS
DESCRIPTION
M_MSTSLV_slv_capt
AV
181
RO
Slave Chiller Total Cap
M_MSTSLV_slv_stat
AV
180
RO
Slave Chiller State
MODES_m_2stpt
BV
64
IR
RO
Second Setpoint In Use
MODES_m_delay
BV
63
IR
RO
Start Up Delay In Effect
MODES_m_demlim
BV
66
IR RO
Demand
Limit
Active
MODES_m_ice
BV
71
IR RO
Ice
Mode
In Effect, Active Alarms:
MODES_m_night
BV
69
IR
RO
Night Low Noise Active
MODES_m_pmpper
BV
68
IR
RO
Pump Periodic Start
MODES_m_pmprot
BV
67
IR RO
Evaporator
Pump
Rotation
MODES_m_reset
BV
65
IR
RO
Reset In Effect
MODES_m_slave
BV
70
IR RO
Master
Slave
Active
MST_SLV_lag_mini
AV
402
RO
Lag Minimum Running Time
MST_SLV_lag_pump
AV
403
RO
Lag Unit Pump Control, 0=Stop if Unit Stops, 1=Run if
Unit Stops
MST_SLV_lead_pul
AV
400
RO
Lead Pulldown Time
MST_SLV_lead_sel
AV
397
RO
Lead Lag Select, 0=Always Lead, 1=Lag Once Failed
Only, 2=Lead/Lag Runtime Sel
MST_SLV_ll_bal_d
AV
398
RO
Lead/Lag
Balance
Delta
MST_SLV_ll_serie
BV
116
RO
Chiller
In
Series
MST_SLV_lstr_tim
AV
399
RO
Lead/Lag
Start
Timer
MST_SLV_ms_ctrl
AV
395
RO
Master Control Type, 1=Local Control, 2=Remote Con-
trol, 3=CCN Control
MST_SLV_ms_sel
AV
394
RO
Master/Slave Select, 0=Disable, 1=Master, 2=Slave
MST_SLV_slv_addr
AV
396
RO
Slave
Address
MST_SLV_start_dt
AV
401
RO
Start If Error Higher
OUTPUTS_ALARM
BV
34
IR RO
Alarm
Relay
Status
OUTPUTS_ALERT
BV
36
IR
RO
Alert Relay State
OUTPUTS_BOX_HTR
BV
57
IR
RO
Control Box Heater
OUTPUTS_C_HEATER
BV
38
IR
RO
Evap Heater Output
OUTPUTS_CAPT_010
AV
70
IR
RO
Chiller Capacity Signal
OUTPUTS_CAPT010A
AV
66
IR
RO
Capacity Signal Cir A
OUTPUTS_CAPT010B
AV
68
IR
RO
Capacity Signal Cir B
OUTPUTS_CP_A
BV
21
IR RO
Compressor
A
OUTPUTS_CP_B
BV
28
IR RO
Compressor
B
OUTPUTS_FCA1
BV
39
IR
RO
Fan Contactor 1A
OUTPUTS_FCA2
BV
40
IR
RO
Fan Contactor 2A
OUTPUTS_FCA3
BV
41
IR
RO
Fan Contactor 3A
OUTPUTS_FCA4
BV
42
IR
RO
Fan Contactor 4A
OUTPUTS_FCA5
BV
43
IR
RO
Fan Contactor 5A
OUTPUTS_FCA6
BV
44
IR
RO
Fan Contactor 6A
OUTPUTS_FCA7
BV
45
IR
RO
Fan Contactor 7A
OUTPUTS_FCA8
BV
46
IR
RO
Fan Contactor 8A
OUTPUTS_FCB1
BV
47
IR
RO
Fan Contactor 1B
OUTPUTS_FCB2
BV
48
IR
RO
Fan Contactor 2B
OUTPUTS_FCB3
BV
49
IR
RO
Fan Contactor 3B
OUTPUTS_FCB4
BV
50
IR
RO
Fan Contactor 4B
OUTPUTS_FCB5
BV
51
IR
RO
Fan Contactor 5B
OUTPUTS_FCB6
BV
52
IR
RO
Fan Contactor 6B
AV
—
Analog Value
IR
—
Intrinsic Reporting
BV
—
Binary Value
RO
—
Read Only
CMD
—
Command
RW
—
Read Write
COV
—
Change of Value
TL
—
Trend Log
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...