Record Configuration Information
PATH
SmartView™ DESCRIPTION
DEFAULT
ENTRY
Login Button
Language
English
Units
US Imp
Main Menu
General Parameters
Setpoint Select
0 (Auto)
Main Menu
Configuration Menu
General Configuration
Cir Priority Sequence
0 (Auto)
Ramp Loading Enable
0 (No)
Unit Off to On Delay
1 min
Demand Limit Type Select
0 (None)
Night Mode Start Hour
0
Night Mode End Hour
0
Night Capacity Limit
100%
Ice Mode Enable
0 (No)
Main Menu
Configuration Menu
Pump Configuration
Evap Pumps Sequence
0 (No Pump)
Pump Auto Rotation Delay
48 hours
Pump Sticking Protection
0 (No)
Flow Checked If Pump Off
1 (Yes)
Main Menu
Configuration Menu
User Config.
User Password
11
Main Menu
Configuration Menu
Reset Configuration
Cooling Reset Select
0 (No reset)
OAT No Reset Value
14° F (–10° C)
OAT Full Reset Value
14° F (–10° C)
Delta T No Reset Value
0 °F (0 °C)
Delta T Full Reset Value
0 °F (0 °C)
Current No Reset Value
0 mA
Current Full Reset Value
0 mA
Space T No Reset Value
14° F (–10° C)
Space T Full Reset Value
14° F (–10° C)
Cooling Reset Deg. Value
0° F (0° C)
Main Menu
Configuration Menu
Factory Parameters
Unit Capacity
Unit Dependent
Power Supply Voltage
Unit Dependent
Energy Management Module
0
Leakage Charge Detection
0
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...