![Carrier AquaForce 30XV140 Controls, Start-Up, Operation, Service And Troubleshooting Instructions Download Page 279](http://html1.mh-extra.com/html/carrier/aquaforce-30xv140/aquaforce-30xv140_controls-start-up-operation-service-and-troubleshooting-instructions_2562366279.webp)
279
APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
*Depends on the selected language (English by default).
TBLSHT — Troubleshoot Info
Carrier Controller PATH:
Main Menu
Maintenance Menu
Troubleshoot Info
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
Evap Entering Fluid
COOL_EWT
—
—
°F (°C)
RO
2
Evap Leaving Fluid
COOL_LWT
—
—
°F (°C)
RO
3
Capacity Signal Cir A
CAPT010A
0 to 100
—
%
RO
4
Cir A Drive Amps
drv_Ia
—
—
A
RO
5
Cir A Drive Speed
drv_Sa
—
—
rpm
RO
6
Saturated Cond Tmp Cir A
SCT_A
—
—
°F (°C)
RO
7
Saturated Suction Temp A
SST_A
—
—
°F (°C)
RO
8
Saturated Liquid Temp A
SLT_A
—
—
°F (°C)
RO
9
Compressor Suction Tmp A
SUCT_A
—
—
°F (°C)
RO
10
Discharge Gas Temp Cir A
DGT_A
—
—
°F (°C)
RO
11
Motor Temperature Cir A
CP_TMP_A
—
—
°F (°C)
RO
12
EXV Eco. Tmp Cir A
ECO_T_A
—
—
°F (°C)
RO
13
Discharge Superheat A
DSH_A
—
—
°F (°C)
RO
14
Suction Superheat A
SH_A
—
—
°F (°C)
RO
15
Liquid Temperature A
LIQ_T_A
—
—
°F (°C)
RO
16
Discharge Pressure A
DP_A
—
—
PSI (kPa)
RO
17
Main Suction Pressure A
SP_A
—
—
PSI (kPa)
RO
18
Oil Pressure A
OP_A
—
—
PSI (kPa)
RO
19
Oil Pressure DifferenceA
DOP_A
—
—
PSI (kPa)
RO
20
Oil Level Input A
OIL_L_A
Off(0)/On(1)
Off(0)
—
RO
21
Oil Solenoid Output A
OIL_SL_A
Off(0)/On(1)
Off(0)
—
RO
22
Economizer Pressure A
ECO_P_A
—
—
PSI (kPa)
RO
23
Liquid Pressure A
LIQ_P_A
—
—
PSI (kPa)
RO
24
-
-
—
—
-
RO
25
Capacity Signal Cir B
CAPT010B
0 to 100
—
%
RO
26
Cir B Drive Amps
drv_Ib
—
—
A
RO
27
Cir B Drive Speed
drv_Sb
—
—
rpm
RO
28
Saturated Cond Tmp Cir B
SCT_B
—
—
°F (°C)
RO
29
Saturated Suction Temp B
SST_B
—
—
°F (°C)
RO
30
Saturated Liquid Temp B
SLT_B
—
—
°F (°C)
RO
31
Compressor Suction Tmp B
SUCT_B
—
—
°F (°C)
RO
32
Discharge Gas Temp Cir B
DGT_B
—
—
°F (°C)
RO
33
Motor Temperature Cir B
CP_TMP_B
—
—
°F (°C)
RO
34
EXV Eco. Tmp Cir B
ECO_T_B
—
—
°F (°C)
RO
35
Discharge Superheat B
DSH_B
—
—
°F (°C)
RO
36
Suction Superheat B
SH_B
—
—
°F (°C)
RO
37
Liquid Temperature B
LIQ_T_B
—
—
°F (°C)
RO
38
Discharge Pressure B
DP_B
—
—
PSI (kPa)
RO
39
Main Suction Pressure B
SP_B
—
—
PSI (kPa)
RO
40
Oil Pressure B
OP_B
—
—
PSI (kPa)
RO
41
Oil Pressure DifferenceB
DOP_B
—
—
PSI (kPa)
RO
42
Oil Level Input B
OIL_L_B
Off(0)/On(1)
Off(0)
—
RO
43
Oil Solenoid Output B
OIL_SL_B
Off(0)/On(1)
Off(0)
—
RO
44
Economizer Pressure B
ECO_P_B
—
—
PSI (kPa)
RO
45
Liquid Pressure B
LIQ_P_B
—
—
PSI (kPa)
RO
46
Comm with Cmp VFD A Ok
VLT_COMA
No(0)/Yes(1)
—
—
RO
47
Comm with Cmp VFD B Ok
VLT_COMB
No(0)/Yes(1)
—
—
RO
48
Comm with Fan VFD A1 Ok
FD_COMA1
No(0)/Yes(1)
—
—
RO
49
Comm with Fan VFD A2 Ok
FD_COMA2
No(0)/Yes(1)
—
—
RO
50
Comm with Fan VFD A3 Ok
FD_COMA3
No(0)/Yes(1)
—
—
RO
51
Comm with Fan VFD B1 Ok
FD_COMB1
No(0)/Yes(1)
—
—
RO
52
Comm with Fan VFD B2 Ok
FD_COMB2
No(0)/Yes(1)
—
—
RO
53
Comm with Fan VFD B3 Ok
FD_COMB3
No(0)/Yes(1)
—
—
RO
LEGEND
RO
—
Read Only
RW
—
Read/Write
Spt
—
Set Point
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...