Input/Output (SIOB) Boards
There are two SIOBs for each unit, SIOB-A (address 49) for Cir-
cuit A and SIOB-B (address 50) for Circuit B. See Fig. 19. These
boards receive inputs from thermistors, transducers, demand limit
switch, dual set point switch, remote on/off switch, chilled water
flow switch, oil level switch, pump interlock contact, compressor
VFD enable contact, and evaporator heater current sensing switch,
and provide output control to expansion valves, oil and variable
load matching solenoids, evaporator heater contactor, isolation
valves, oil heater relays, customer supplied pump relays, compres-
sor VFD enable relays, and customer-supplied alarm and running
relays. Information is transmitted between the SIOBs and the
Carrier Controller module via a 3-wire communication bus or
LEN bus. Connections for the LEN bus are J12 and J13. Each
SIOB has a 4-position DIP switch bank used for addressing of the
board. SIOB-A is at address 49 and SIOB-B is at address 50. See
Table 6 for SIOB DIP switch settings. See Tables 7 and 8 for a list
of inputs and outputs for the two SIOBs.
Fig. 19 — SIOB
Table 6 — SIOB A and B DIP Switch Settings
SIOB-A DIP Switch
1
2
3
4
Position
OFF
OFF
OFF
OFF
SIOB-B DIP Switch
1
2
3
4
Position
ON
OFF
OFF
OFF
a30-5864
DIP
S
WITCH
GREEN LED - LEN
(Loc
a
l E
qu
ipment Network)
RED LED -
S
TATU
S
LEN CONNECTION
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...