APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
*
Depends on the selected language (English by default).
SERVICE — Service Parameters Table
Carrier Controller PATH:
Main Menu
Configuration Menu
Service Parameters
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
Evaporator Fluid Type
flui_typ
1 to 3
1
—
RW
1=Water, 2=Med Brine, 3=Low Brine
2
Entering Fluid Control
ewt_opt
No(0)/Yes(1)
No(0)
—
RW
3
Brine Freeze Setpoint
freezesp
-20 to 34 (-28.9 to
1.1)
34(1.1)
°F(°C)
RW
4
Brine Minimum Fluid Temp
mini_lwt
-20 to 38 (-28.9 to
3.3)
38(3.3)
°F(°C)
RW
5
Fast Capacity Recovery
fastcapr
0 to 2
0
—
RW
0=Disabled
1=Quickstart Load
2=Fast Capacity Recov
6
EWT Probe on Cir A Side
ewt_cirA
No(0)/Yes(1)
Yes(1)
—
RW
7
Service Password
ser_pass
0 to 9999
88
—
RW
8
Leakage Charge Threshold
leak_thr
0 to 10
2.5
Volts
RW
9
Leakage Charge Timer
leak_tmr
0 to 600
60
min
RW
10
Compressor RFI Filter En
RFI_conf
Off(0)/On(1)
On(1)
—
RW
11
Metric Units? (Blackbox)
metric
No(0)/Yes(1)
No(0)
—
RW
12
Send Fan Drive Config?
fdrv_cfg
No(0)/Yes(1)
Yes(1)
—
RW
13
Send Comp. Drive Config?
cdrv_cfg
No(0)/Yes(1)
Yes(1)
—
RW
14
Evap Heater Delta Spt
heatersp
0 to 6.0
2.0
—
RW
15
Freeze Override Offset
freez_ov
0 to 5.8(-17.8 to -
14.6)
0(-17.8)
°F(°C)
RW
16
Auto Start When SM Lost
auto_sm
Disable(0)/Enable(1)
Disable(0)
—
RW
17
VI Self-Test Threshold
ViPwrChk
0.5 to 15
1.15
KW
RW
18
VI Self-Test Enable
ViChkEn
Off(0)/On(1)
Off(0)
—
RW
19
Pump Rot. AntiFrz Protec
AntiFrz
Off(0)/On(1)
On(1)
—
RW
20
Oil Delta Trigger Speed
odtrgspd
0 to 15
5
Hz
RW
21
Oil Trigger Time
otrigtim
600 to 7200
3600
seconds
RW
22
Oil Delta Recovery Speed
odrecspd
0 to 15
5
Hz
RW
23
Oil Recovery Time
orectim
30 to 120
60
seconds
RW
24
Water Temp Hysteresis
wateesys
0.9 to 10
0.9
Volts
RW
25
Enable High VI at Start
vistrten
Disable(0)/Enable(1)
Enable(1)
—
RW
26
High VI Time at Start
vistrtdt
0 to 3600
900
Tons/H
RW
27
Approach Ctrl at Start?
apr_en
No(0)/Yes(1)
Yes(1)
—
RW
LEGEND
RW
—
Read/Write
Spt
—
Set Point
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...