APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
*Depends on the selected language (English by default).
M_MSTSLV — Master Slave Control
Carrier Controller PATH:
Main Menu
Maintenance Menu
Master Slave Control
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
MASTER/SLAVE CONTROL
—
—
—
—
—
2
Unit is Master or Slave mstslv
Disable(0)/
Enable(1)
Disable(0)
—
RO
3
Master Control Type
ms_ctrl
—
—
—
RO
4
Master/Slave Ctrl Active
ms_activ
False(0)/True(1)
False(0)
—
RO
5
Lead Unit is the:
lead_sel
Master(0)/Slave(1)
Master(0)
—
RO
6
Slave Chiller State
slv_stat
—
—
—
RO
7
Slave Chiller Total Cap
slv_capt
0 to 100
—
%
RO
8
Lag Start Delay
l_strt_d
—
—
min
RO
9
Lead/lag Hours Delta
ll_hr_d
—
—
hours
RO
10
Lead/lag Changeover?
ll_chang
No(0)/Yes(1)
No(0)
—
RO
11
Lead Pulldown ?
ll_pull
No(0)/Yes(1)
No(0)
—
RO
12
Master/Slave Error
ms_error
—
—
—
RO
13
Max Available Capacity ?
cap_max
No(0)/Yes(1)
No(0)
—
RO
14
Slave lagstat
lagstat
—
—
—
RO
15
Slave Operating Hours
slav_hr
—
—
hours
RO
16
Slave Evap Ent. Fluid
slav_ewt
—
—
°F (°C)
RO
17
Slave Evap Leav. Fluid
slav_lwt
—
—
°F (°C)
RO
ECO_CTRL — EXV Eco. Control
Carrier Controller PATH:
Main Menu
Maintenance Menu
EXV Eco. Control
LINE
DISPLAYED TEXT*
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
EXV Eco Pos. (Pct) A
eco_a
0 to 100
—
%
RO
2
EXV Eco Pos. (Steps) A
eco_stpa
0 to 10000
-—
-
RO
3
Eco Suction Superheat A
eco_sh_a
—
—
°F (°C)
RO
4
Eco Suction SH Setpt A
esh_sp_a
-—
-—
°F (°C)
RO
5
EXV Eco State A
eco_sta
—
—
—
RO
6
EXV Eco Previous State A
eco_lsta
-—
-—
-—
RO
7
EXV Eco Wished Pos A
ecowposa
—
—
—
RO
8
EXV Eco Mode A
eco_moda
-—
-—
-—
RO
9
EXV Eco Mode Txt A
eco_txta
—
—
—
RO
10
EXV Eco Pos. (Pct) B
eco_b
0 to 100
-—
%
RO
11
EXV Eco Pos. (Steps) B
eco_stpb
0 to 10000
—
-
RO
12
Eco Suction Superheat B
eco_sh_b
—
-—
°F (°C)
RO
13
Eco Suction SH Setpt B
esh_sp_b
-—
—
°F (°C)
RO
14
EXV Eco State B
eco_stb
—
-—
—
RO
15
EXV Eco Previous State B
eco_lstb
-—
—
-—
RO
16
EXV Eco Wished Pos B
ecowposb
—
-—
—
RO
17
EXV Eco Mode B
eco_modb
-—
—
-—
RO
18
EXV Eco Mode Txt B
eco_txtb
—
-—
—
RO
LEGEND
RO
—
Read Only
RW
—
Read/Write
Spt
—
Set Point
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...