CL-5
Record Configuration Information
PATH
SmartView™ DESCRIPTION
DEFAULT
ENTRY
Main Menu
Configuration Menu
Service Parameters
Evaporator Fluid Type
1 (Water)
Entering Fluid Control
no
Brine Freeze Setpoint
34° F (1.1° C)
Brine Minimum fluid temp
38° F (3.3° C)
Fast Capacity Recovery
0
EWT Probe on cir A side
yes
Service Password
88
Leakage Charge Threshold
2.5 Volts
Leakage Charge Timer
60 min.
Compressor RFI Filter En
on
Metric Units?
no
Send fan drive config?
yes
Send comp. Drive config?
yes
Evaporator Heater Delta Spt
2 (Number of deg added to brine freeze
setpoint to enable heater)
Freeze override offset
0 °F (0 °C)
Auto Start When SM Lost
0 (disable)
VI Self-Test Threshold
1.15 kW
Pump Rot. AntiFrz Protec
on
Main Menu
Configuration Menu
Master Slave Config
Master/Slave Select
0 (disable)
Master Control Type
1 (Local)
Slave Address
2
Lead Lag Select
0 (Always Lead)
Lead/Lag Balance Delta
168 hours
Lead/Lag Start Timer
10 min
Lead Pulldown Time
0 min
Start If Error Higher
4 °F (2.2 °C)
Lag Minimum Running Time
0 min
Lag Unit Pump Control
0 (Stop if Unit Stops)
Chiller In Series
0 (No)
Main Menu
Setpoint Table
Cooling Setpoint 1
44° F (6.7° C)
Cooling Setpoint 2
44° F (6.7° C)
Cooling Ice Setpoint
44° F (6.7° C)
Cooling Ramp Loading
1°F (0.6 °C)
Switch Limit Setpoint 1
100%
Switch Limit Setpoint 2
100%
Switch Limit Setpoint 3
100%
LEGEND
Spt
— Set Point
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...