Description
Symbol
Unit
KMV03.1R-
A05K0-P-D7-
ET-NNNN
KMV03.1R-
B0007-P-D7-
ET-NNNN
KMV03.1R-
I01K5-P-D7-
ET-NNNN
KMV03.1R-
W06K0-P-D7-
ET-NNNN
Mains
fuse
according
to
EN 60204‑1
A
20
30
6
20
Required wire size in accordance
with NFPA 79 and UL 508 A
(internal wiring);
5)
A
LN
AWG
14
Latest amendment: 2019-08-08*
1) 2)
Mains voltage > U
LN
: Use a transformer with grounded neutral
point, do not use autotransformers!
3)
Otherwise use HNL mains choke
4)
Observe allowed number of switch-on processes; without ex‐
ternal capacitors at the DC bus
5)
Copper wire; PVC-insulation (conductor temperature 90 °C;
T
a
≤ 40 °C) in accordance with NFPA 79 chapter 12 and
UL 508A chapter 28
Tab. 5-13:
KMV - Mains voltage supply data
98/407
Technical data of the components
IndraDrive Mi Drive Systems with KCU02, KSM02,
KMS02/03, KMV03, KNK03, KLC03
Bosch Rexroth AG R911335703_Edition 04