BVS ID-M1280xF1-xx-xxx
english
137
ISDU
Name
Inde
x
Subin
dex
Acc
ess
Leng
ht
Data
Type
Data
Storag
e
Default
Voltage
Monitoring
Detection Time
Duration
0x22
00
(870
4)
0
R/W
2
byte
s
UINT16
Yes
10
Voltage Monitoring Detection Time Duration
This parameter is used to define how long the undervoltage or over-voltage must be present before it is
displayed. The unit is given in milliseconds. The values must be in the range between 10 and 1000, in
increments of 5 milliseconds. The default value is 10 milliseconds.
System Commands
Command Value
Device Action
0x81 (129)
Application Reset – Resets the Voltage Monitoring Detection Time Duration with
ISDU-index 0x2200 to the default value 10.
0x82 (130)
Reset Factory Settings – Resets the Voltage Monitoring Detection Time Duration
with ISDU-index 0x2200 to the default value 10.
Events
Event
Code
Event Type
Event – Description – Remedy
Device Status
0x5110
(20752)
Warning
Primary supply voltage exceeded
→
Check for deviations in the supply.
2 – Out-of-Specification
0x5111
(20753)
Warning
Primary supply voltage below minimum value
→
Check for deviations in the supply.
2 – Out-of-Specification
0x8D0B
(36107)
Warning
Overload or short circuit at pin 1
→
Check wiring.
2 – Out-of-Specification
0x8D0D
(36109)
Warning
Incorrect load/cable breakage, analog current
output pin 1
→
Check wiring or connected devices.
2 – Out-of-Specification
0x8D15
(36117)
Warning
Overload at pin 1
→
Check wiring.
2 – Out-of-Specification
Extreme Environment Status
Description
With the help of the Extreme Environment Status, the time is recorded in which the
BVS ID
was exposed to
extreme conditions. In parameter Lifetime Extreme Thresholds, limit values can be configured for the respective
Summary of Contents for BVS ID-M1280-F1 Series
Page 1: ...deutsch Konfigurationsanleitung english Configuration Guide BVS ID M1280 F1 xx xxx...
Page 2: ...www balluff com...
Page 3: ...deutsch Konfigurationsanleitung BVS ID M1280xF1 xx xxx...
Page 4: ...www balluff com...
Page 79: ...BVS ID M1280xF1 xx xxx deutsch 77 Ablaufdiagramm Handshake...
Page 81: ...BVS ID M1280xF1 xx xxx deutsch 79 Ablaufdiagramm Handshake mit Input Toggle...
Page 83: ...BVS ID M1280xF1 xx xxx deutsch 81 Ablaufdiagramm Handshake mit Output Toggle...
Page 173: ...956115_AA DE K22 nderungen vorbehalten...
Page 174: ......
Page 175: ...english Configuration Guide BVS ID M1280xF1 xx xxx...
Page 176: ...www balluff com...
Page 245: ...BVS ID M1280xF1 xx xxx english 71 Handshake flow chart...
Page 247: ...BVS ID M1280xF1 xx xxx english 73 Handshake flow chart with input toggle...
Page 249: ...BVS ID M1280xF1 xx xxx english 75 Handshake flow chart with output toggle...