Trouble shooting 15
OUTDOOR UNIT
OUTDOOR UNIT
Error Method:
Error Method:
PUMP DOWN ABNORMAL
(HIGH PRESSURE)
Detective Actuators:
Detective Actuators:
Pressure SW1 (Hi pressure) OPEN
Detective details:
Detective details:
During the pump – down operation, the pressure switch 1 becomes OFF
(More than 4.2Mpa was detected.)
Indicate or Display:
Indicate or Display:
Indoor Unit :
Operation LED
Flash
Flash
,
,
Timer LED
3 Times Blink
3 Times Blink
Swing LED
3 Times Blink
3 Times Blink
Outdoor Unit :
LED1
Flash
Flash
,
,
LED2
9
9
Time
Time
s
s
Blink
Blink
ERROR CODE: E:32
Forecast of Cause
Forecast of Cause:
1. 3 way valve was not open 4. Check for Outdoor Unit fan
7. Check Indoor unit Fan rotation
2. Check around Pressure SW 1 5. Check EEV1 operation
3. Amount of refrigerant
6. Check EV - KIT operation
Check Point 2 :
Check Point 2 :
Check around Pressure SW 1
Check around Pressure SW 1
Check removed connection or cable cut off.
Check around Pressure SW 1
(PARTS INFORMATION 8)
(PARTS INFORMATION 8)
Replace Pressure SW1 if it is defective, and check the
operating condition.
Check Point 5 : Check Outdoor unit EEV1
Check Point 5 : Check Outdoor unit EEV1
Check around Outdoor unit EEV1
(PARTS INFORMATION 10)
(PARTS INFORMATION 10)
If Outdoor unit EEV1 is defective , replace it
Check Point 3 : Check Out of Refrigerant
Check Point 3 : Check Out of Refrigerant
Check if the refrigerant amount is proper by measuring Gas pressure.
(Condensation temp., Refrigerant Pressure Chart) Refer Service manual 8-4-2
When the refrigerant is recharged, make sure to perform the vacuuming and charge
the originally specified amount.
Check Point 1 : Check valve opening
Check Point 1 : Check valve opening
If the valve was closed, open it and check the condition.
Check Point 4 :
Check Point 4 :
Check for Outdoor Unit fan
Check for Outdoor Unit fan
Check the fan hand and check if it turns normal.
Check around Outdoor fan motor
(Parts Information 6)
(Parts Information 6)
Check if the air flow route of Outdoor unit fan is blocked.
If Outdoor fan motor is defective, replace it.
Check Point 6 : Check EV - KIT
Check Point 6 : Check EV - KIT
Check around EV - KIT
(PARTS INFORMATION 11)
(PARTS INFORMATION 11)
Replace EV - KIT if it is defective.
Check Point 7 : Check Indoor unit Fan rotation
Check Point 7 : Check Indoor unit Fan rotation
At the stop operation, turn the fan by hand and check if it rotes.
Check if it the filter clogged.
Check if the fan is loose from the shaft.
If either fan or bearing is defective, replace it.
06-19
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...