1) Connection cable wiring
Check Point 2 : Check Outdoor unit Filter PCB
Check Point 2 : Check Outdoor unit Filter PCB
1)Check wiring of Power cord / Connection cable (incorrect wiring, loose wiring, etc.)
2)Check Power Supply AC220 + - 20V between Outdoor unit terminal 1-2.
If it is NG, Check the power cord at the circuit breaker side
3)Check Varistor (VA202,VA203)
If it is NG, Check if power supply other than the specified one is connected.
If Varistor is defective, replace it.
4)Check FUSE (F201)
If it is open, check the shortage between L – N and replace the FUSE
5)Check the voltage (AC 220V) between Power Supply W203 – V204.
If it the voltage is abnormal, replace Filter PCB Check CT
(
(
PARTS INFORMATION 1)
PARTS INFORMATION 1)
6)Check FUSE (F203)
If FUSE is open, check the cause of open and replace the FUSE.
7)Check VA201
If it Varistor is defective, check the primary side voltage and replace the varistor.
2. OUTDOOR UNIT NO POWER
1) Check Power Relay
(PARTS INFORMATION 2)
(PARTS INFORMATION 2)
2) Check Diode Bridge
(PARTS INFORMATION 3
(PARTS INFORMATION 3)
3) Check Active filter module (
PARTS INFORMATION 4
PARTS INFORMATION 4)
Check Point 3 :
Check Point 3 :
Check the parts around Filter PCB
Check the parts around Filter PCB
1)Check DC 300V + - 20V at CN10 of Control PCB.
If -20V does not appear, Check Capacitor
2)Check Fuse (F1) of Control PCB
If the FUSE is open, locate the cause of open and replace the fuse.
If another abnormal is found, replace Control PCB.
Check Point 4 :
Check Point 4 :
Check
Check
Outdoor unit Controller PCB
Outdoor unit Controller PCB
VA202,VA203 : P/No. 0000361224
F201: P/No.0600222512
F203 : P/No. 0600385163
VA201 : P/No. 0000361101
Forecast of Cause
Forecast of Cause:
1. Relation of installation construction 3. Check the parts around Filter PCB
1) Use of specified material
1) Check Power Relay
2) Check the power supply
2) Check Diode Bridge
3) Check Active Filter Module
2. Relation of Outdoor unit filter PCB
4.Relation of Outdoor unit Controller PCB
2) Check Power supply
1) Check DC Input
3) Check Varistor of Outdoor unit
2) Check FUSE(F1)
4) Check Fuse of Outdoor unit
5) Check CT of Filter PCB
Check Point 1
Check Point 1
-
-
2 : Check Power supply
2 : Check Power supply
Check external cause (Power supply)
Instant Drop
Check if there is an electric equipment with a large load in the same circuit.
Instant Power Outage
Check if there is a defective contact or leakage in the power supply.
Noise
Check if there is any equipment that cause the harmonic wave near the power line.
(Neon tube or Electric equipment that harmonic wave Check that the grounding is completely insulated.)
30A
Circuit breaker
H07RN-F or
Equivalent
Min.5.0mm
Total length is
less than 50m
Connection cord
H07RN-F or
Equivalent
Max. 8.0mm
Min.5.0mm
Power supply
cord
Wire type
Size
Use
Check Point 1
Check Point 1
-
-
1 : Check the installation work
1 : Check the installation work
Follow the installation Manual if any installation failure is found.
Check Cable / Breaker Check if any loose connection or removal of cable.
2
2
2
06-38
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...