During the test run operation, check the following items.
When the power supply turn on,check the following items.
Outdoor unit : LED 1 lights continuously.
if LED flushing, it means error occurs ,check the eroor and solve the problem.
Indoor unit : LED RED (operation lamp) & GREEN (timer lamp) lights flush alternately.
RC : CLOCK display indicates
When errors occur, don't advance towards the following step before a complete settlement of all these errors.
Start the Indoor unit test run from remote controller one by one (Refer to 1-3-2)
Check the following item.
Indoor unit
LED (red&green) light flush at the same time slowly.
Louver operates to open.
Fan rotates
Air flow comes
(Drain pump opration)
RC signal receive
Outdoor unit
Coresponds from indoor unit signal
Compressor start to operates
Fan rotates
Measure the following item.
Indoor unit
Air intake temp.
Air flow temp.
Outdoor unit
Outdoor temp.
Discharge pipe temp.
Suction pipe temp.
High pressure
Low pressure
Frequency of compressor
Continue the operation about 10 minutes.
When there is no ploblem, check the next indoor unit.
After every indoor unit is check by test run, please do test run using all of the indoor units and check them.
1
2
3
4
01-05
Outdoor
unit
Indoor
EV kit
unit
Wired
remote controller
Connection cable
1 50Hz 220 - 240V
No abnormal sound and vibration.
No abnormal sound and vibration.
1-2-2 Ceck Item Durring Test Run
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...