SERVICE
SERVICE
PARTS
PARTS
INFORMATION 6
INFORMATION 6
Compressor ASSY
Check Point 3: Check Winding resistance
Check Point 3: Check Winding resistance
Check between each terminal of resistance value.
Resistance
Resistance
Value
Value
0.187
0.187
U
U
V
V
W
W
U
U
(RED)
(RED)
V
V
(WHITE)
(WHITE)
W
W
(BLACK)
(BLACK)
P
U
V
W
N
Check Point 1: Check Circuit connection
Check Point 1: Check Circuit connection
Check the connection to each terminal.
If the resistance value is either 0 or
, replace Compressor
TR PWB ASSY
Terminal cover opened
Terminal cover opened
P/No.
9372716014 (Compressor ASSY)
Check Point 4: Check condition of cooling Test Operation
Check Point 4: Check condition of cooling Test Operation
30rps.
50rps.
30sec.
180sec.
Check Compressor speed at Test Operation
P
U
V
W
N
TR PWB ASSY
Permanent Magnet is 6 polar
Permanent Magnet is 6 polar
1cycle is 3 Hz.
1cycle is 3 Hz.
Check Point 2: Check Operation
Check Point 2: Check Operation
Check Pressure when compressor operate.
1) Pressure decreases when the refrigerant is less. 2) Pressure decrease when the Piping is blocked.
Check discharge temperature when compressor operate.
1) Temperature rises when the refrigerant is less.
Check operating current when compressor operate.
1) Operating current rises when the refrigerant is less. 2) Operating current rises when the compressor is rock.
06-48
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...