4-4 EXPANSION VALVE CONTROL
(1) Initialization
When power in turned on
When the operation mode becomes off
(2) Number of pulse at the stop operation
500 pulses
(3) Operation Control
During the operation, the electronic expansion valve detects the discharge gas temperature
value and is automatically controlled by the feed back control so that it is kept at the target
value.
Control pulse range : 100 to 500 pulses
The targeted discharge temperature differs depending on the indoor operation capacity,
compressor rotation speed and outdoor temperature.
4-5 4-WAY VALVE CONTROL
It selects either cooling or heating.
Cooling mode : OFF
Heating mode : ON
Stop
: OFF
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...