01-06
CHECK LIST
Check item
Checking Method
1
2
Standard
High pressure and low pressure
are normal?
Confirm with a pressure gauge
Cooling : Low pressure 0.7 to 0.9MPa (approx.)
Heating : High pressure 2.2 to 2.7 MPa (approx.)
3
Intake and outlet air Temperature
of indoor unit are normal?
Check that there is a difference
between the intake and outlet air
temperatures.
Check operation sound of the
drain pump.
4
5
Water is drained from drain hose
or by the drain pump smoothly?
(Only for cooling mode)
Confirm water is draining.
Cooling : Below -10 C (approx.)
Heating : Above 15 C (approx.)
Expansion valve of the stopped
indoor unit are normal?
Check the refrigerant flows to the
heat exchanger.(Wait at least 5
minutes after the indoor unit has
stopped before checking the
refrigerant.)
Cooling : No refrigerant flow
Heating : A little refrigerant flow
After operating the indoor unit,
the compressor operates?
Check operation sound and
the LED of outdoor unit PCB.
Outdoor unit LED 3 :flushing
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...