04-03
4-2 COMPERESSOR OPERATION
4-2-1 Capacity control
COOLING
HEATING
The rotation speed of the compressor is decided basing on the sum of the required refrigerant amount from
the connected indoor units.
The rotation speed of the compressor is decided by detecting the indoor heat exchanger mid temperature
of the connected indoor units which is running on heating mode, so that the temperature reaches to the
target temperature.
The compressor is controlled by PI control.
The one of the largest value of the signals from the indoor units on heating operation during the heat exchanger
temperature detection is used to decide the rotation speed.
However, the rotation speed of the compressor at start-up is decided basing on the sum of the required refrigerant
amount.
4-2-2 Frequency control
On stop mode 0Hz
On operating mode 20Hz 101Hz
Minimum running frequency 20Hz
Correction
The correction of control frequency of the compressor is done by the following
conditions.
Outdoor Temperature
Pipe Length Setting
Capacity Shift Setting
Protective Operation
Note that the protective correction has the most priority when the protection function is activated.
Limit
Operation current limits as accordance with DIP-SW setting.
Rotation speed hold
When compressor starts from stop condition rotation speed keep ones holding at followings.
Hold 1 : 30sec at 30Hz
To prevent from cut down low pressure
Hold 2 : 3 min at 50Hz
To stabilized the oil level
30Hz
50Hz
30sec.
3 min
Hold 1
Hold 2
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...