Trouble shooting 30
OUTDOOR UNIT
OUTDOOR UNIT
Error Method:
Error Method:
EEPROM ERROR
Detective Actuators:
Detective Actuators:
Outdoor unit Control PCB
Detective details:
Detective details:
When the access to the external memory (EEPROM) is failed due to some
cause (External Noise, defective component,etc.) upon Outdoor Unit start
– up. After the error occurred, the operation of Outdoor unit is not limited.
1)Check the supply voltage AC220V between (L) and (N)
If AC does not appear, check the circuit at power supply side.
2)Check the wiring of connection cable (incorrect wiring / loose connection, etc.)
If there is incorrect or loose wiring, turn off the breaker and conduct rework.
Check Point 2
Check Point 2
-
-
1 : Check Power cord Connection
1 : Check Power cord Connection
Forecast of Cause
Forecast of Cause:
1.Relation of installation construction
2. Relation of unit
1) Use of specified material
1) Check the Power POWER CORD
2) Power supply circuit (voltage drop/ Noise etc.)
2) Check Control PCB(Component failure)
Check Point 2
Check Point 2
-
-
2 :
2 :
Check Outdoor Unit electrical components.
Check Outdoor Unit electrical components.
Check connection, removal and incorrect wiring of all the connectors.
Check if any shorted mark or corrosion on PCB
When Control PCB is defective, replace it.(If Dip SW was changedconduct resetting DIP SW.)
Check Point 1
Check Point 1
-
-
2 : Check Power supply
2 : Check Power supply
Check external cause (Power supply)
Instant Drop
Check if there is an electric equipment with a large load in the same circuit.
Instant Power Outage
Check if there is a defective contact or leakage in the power supply.
Noise
Check if there is any equipment that cause the harmonic wave near the power line.
(Neon tube or Electric equipment that harmonic wave Check that the grounding is completely insulated.)
Indicate or Display:
Indicate or Display:
Indoor Unit :
Operation LED
Flash
Flash
,
,
Timer LED
3 Times Blink
3 Times Blink
Swing LED
3 Times Blink
3 Times Blink
Outdoor Unit :
LED1
Flash
Flash
,
,
LED5
3
3
Time Blink
Time Blink
ERROR CODE: E:32
30A
Circuit breaker
H07RN-F or
Equivalent
Min.5.0mm
Total length is
less than 50m
Connection cord
H07RN-F or
Equivalent
Max. 8.0mm
Min.5.0mm
Power supply
cord
Wire type
Size
Use
Check Point 1
Check Point 1
-
-
1 : Check the installation work
1 : Check the installation work
Follow the installation Manual if any installation failure is found.
Check Cable / Breaker
Check if any loose connection or removal of cable.
2
2
2
06-33
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...