Trouble shooting 27
OUTDOOR UNIT
OUTDOOR UNIT
Error Method:
Error Method:
CT ERROR
Detective Actuators:
Detective Actuators:
Ct abnormal of Power PCB is detected by
Control PCB detection circuit
Detective details:
Detective details:
When the compressor speed become more than 50 Hz after the start up,
the compressor stops if Outdoor unit current (Compressor current)
becomes less than 8.0A that was detected by the input current sensor (CT).
If this operation occurs 2 times continuously, the compressor becomes
permanent stop.
Then LED indicates error, and the error information is output to the network.
Forecast of Cause
Forecast of Cause:
1. Connection electrical parts
4. Reactor (Coil) is open or short to other circuit
2. Power PCB (CT) defective
5. Check TR PWB ASSY
3. Diode bridge defective
Check Point 1 : Check connection electrical parts
Check Point 1 : Check connection electrical parts
Check if any incorrect wiring at connectors of electrical parts
Check the cable wiring between Filter PCB and Control PCB (CN 202-CN11)
Correct the connection mistake or erroneous connection of connector.
Check Point 2 : Check Power PCB (CT)
Check Point 2 : Check Power PCB (CT)
Remove connector CN11 and check the resistance at both terminals (560ohm).
If it is not possible to check the resistance value, replace Power PCB
Check Point 3 : Check Diode bridge
Check Point 3 : Check Diode bridge
Remove the connector and measure the resistance value at each terminal by following procedure.
Check Diode bridge
(PARTS INFORMATION 3)
(PARTS INFORMATION 3)
Check Point 4 : Check Reactor (Coil)
Check Point 4 : Check Reactor (Coil)
Remove the connector and check if each terminal is open or if there is a short circuit in the electrical box.
Indicate or Display:
Indicate or Display:
Indoor Unit :
Operation LED
Flash
Flash
,
,
Timer LED
3 Times Blink
3 Times Blink
Swing LED
3 Times Blink
3 Times Blink
Outdoor Unit :
LED1
Flash
Flash
,
,
LED4
6
6
Time Blink
Time Blink
ERROR CODE: E:32
Check Point 2 : Diagnosis of TW PWB ASSY
Check Point 2 : Diagnosis of TW PWB ASSY
1.If error appears during the compressor running, check if each voltage between U – V,V – W, W – U are output in a good valance.
If the voltage value comparison between each terminal is abnormal when the rotation frequency is constant, replace
TW PWB ASSY.
2. Check TR ASSY(Judgment of Transistor module)
Check the continuity by removing each terminal cable.
Replace TR ASSY if it is abnormal.(Compare with the table on right)
06-30
P
U
V
W
N
TR PWB ASSY
(+),( - ) shows the terminal of the meter
Outdoor unit grille side
14 15
N ( )
N ( )
W ( )
V ( )
14 15
U ( )
P ( )
V ( )
U ( )
W ( )
V ( )
U ( )
P ( )
W ( )
V ( )
U ( )
W ( )
Normal
resistance
value
COMP
TERMINAL
P / N
TERMINAL
Multimeter
Resistance value
U
1M Ohm or greater
U
W
V
P
W
V
N
The resistance value is changes in a type
of the tester (Digital or Analogue)
and internal resistance.
Confirm method for analog meter.
Simple confirm method for digital meter.
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...