1. INDOOR UNIT NO POWER
Check Point 2 : Check
Check Point 2 : Check
Indoor unit Filter PCB
Indoor unit Filter PCB
Forecast of Cause
Forecast of Cause:
1.Relation of installation construction 2. Relation of Indoor unit Filter PCB
1)Use of specified material 1)Wiring of connection cable
2)Check the power supply 2)Check power supply
3)Check Fuse of Indoor unit filter PCB
4)Check varistor of Indoor unit filter PCB
5)Check Power PCB
6)Check Thermal Fuse of Indoor unit
3. Relation of Indoor unit Filter PCB
Checking method when all Indoor unit do not turn ON.
Checking method when all Indoor unit do not turn ON.
Checking method when certain Indoor unit does not turn ON.
Checking method when certain Indoor unit does not turn ON.
1)Check the wiring (incorrect wiring, loose wiring , etc.)of connection cable.
2)Check Power Supply voltage AC220 + - 20V between Indoor unit terminal 1- 2.
If it is NG, trance the connection cable at Outdoor unit side.
3)Check FUSE(F101) of Filter PCB
If it is NG, Check shortage of L – N or cable wiring, then replace FUSE.
4)Check Varistor of Filter PCB (VA102,VA101)
If it is NG, check if the specified power voltage is supplied and replace Varistor.
5)Remove CN1 from Control PCB, and check AC 220V +- 20V.
If it is NG, replace Power PCB.
6)Check the continuity of Terminal FUSE(Only for Wall mounted and Cassette Type)
If it is NG, check the the material and dielectric voltage, and replace Thermal FUSE.
1)Check above items 1) through 7)
2)Check the insulation between terminal 1 –2 of Outdoor unit.
If it is NG, remove the connection cable from the terminal Indoor unit and trace the abnormal condition.
Check Point 1
Check Point 1
-
-
2 : Check Power supply
2 : Check Power supply
Check external cause (Power supply)
Instant Drop
Check if there is an electric equipment with a large load in the same circuit.
Instant Power Outage
Check if there is a defective contact or leakage in the power supply.
Noise
Check if there is any equipment that cause the harmonic wave near the power line.
(Neon tube or Electric equipment that harmonic wave Check that the grounding is completely insulated.)
6- 4-2 TROUBLE SHOOTING WITH NO ERROR CODE
30A
Circuit breaker
H07RN-F or
Equivalent
Min.5.0mm
Total length is
less than 50m
Connection cord
H07RN-F or
Equivalent
Max. 8.0mm
Min.5.0mm
Power supply
cord
Wire type
Size
Use
Check Point 1
Check Point 1
-
-
1 : Check the installation work
1 : Check the installation work
Follow the installation Manual if any installation failure is found.
Check Cable / Breaker Check if any loose connection or removal of cable.
3)Check the power supply of Outdoor unit.
Refer to
Trouble shooting 2
Trouble shooting 2
OUTDOOR
OUTDOOR
UNIT
UNIT
NO POWER.
NO POWER.
Check Point 3 : Check Outdoor unit
Check Point 3 : Check Outdoor unit
2
2
2
06-37
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...