Before test run, check the following items.
EV kit
Is the selection of the outdoor unit and the indoor units correct?
(Check the number of connected indoor units, total capacity of the indoor units)
Is the piping length correct?
(Ex. Maximum piping length : 70m)
Doesn't gas leak?
Have the vaccuum process done enough time?
Is the refrigerant flow correct?
1
4
Is the unit installed correct?
2
Is the unit installed with enough service space and without air obstacle?
3
Is the additional refrigerant charge amount correct?
Are the power supply cables connected?
Is the spec. for the power supply cable correct?
Is the spec. for connection cable correct?
(3 wire , 2.5mm )
Is the connection cable connected to all the units?
Is the remote controller cable connected correct?
Are the addresses set?
5
7
8
9
10
11
12
Is the voltage of power suppy within proper range?
13
Is the diameter and thickness of the selected pipe correct?
6
Is the EV kit connected to all the unit?
14
16
18
Is the EV kit connection cable connected correct?
17
19
20
21
22
Have the all settings done on the PCB?
23
Is the 3 way valve opened?
24
Is the pipe heat-insulated which have the enough thickness?
(Humidity 70% :10mm, 70 80% :15mm, 80% :20mm)
Is the drain water-flow correct?
Is the power supplied to unit for more than 12 hours before the start of test run at outdoor
temperature of 20 or below?
1 50Hz 220 - 240V
1-2 CHECK ITEM
01-04
15
12
11
1 2 3
21 23 24
10
13
1-2-1 Check Item Before Test Run
16 19 20 23
16 19 20 23
16 19 20 23
2
6 17
3 16 19 20
2
Is the connection cable connected correct?
4 5 7 8 9 22
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...