06-49
SERVICE
SERVICE
PARTS INFORMATION 7
PARTS INFORMATION 7
FAN Motor Outdoor unit
Check Point 1: Check Circuit connection
Check wiring of connectors between Control PCB CN2 - Joint Connector - Fan motor
Check FAN capacitor connect (Yellow / Black)
RED(2) - BLUE(3)
WHITE(1) - RED(2)
RESISTANCE VALUE ( )
READ WIRE
Check Point 2: Check Open / Short of circuit
If it is abnormal, replace Fan motor
Check open / short of the coil in Fan Motor
P/No.
9601705017 (Motor induct )
Control signal
Check Point 3: Check Fan motor Power supply
Check Output voltage of CN2.
As stand – by, check / -20V between CN2(2) - CN1(2)
If it is 0 V, check the connection of AC IN (CN1) or Power
supply
Check Point 4: Check around Fan motor
Check if there is an obstruction of air flow route to Fan Motor.
Too close to Wall / Dirt / Mud
Main B
Main A
Protector
Capacitor
Au
x
Lo BLUE
Hi RED
COM. WHITE
YELLOW
BLACK
ITEM
Main A
Main B
Aux
RED(2) - BLACK
45.0 5%
22.5 5%
59.5 5%
DC12V
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...