Description
Indoor unit
Remote indication
Indicates that the power came on normally when power
was applied (at power failure recovery). Indication is
cleared by RUN command.
The red and green lamps flash
alternately in the operation stop
state.
When test run is performed, the unit operates
without regard to the temperature setting. Stopped by
remote controller stop. or reset after 60 minutes.
The red and green lamps flash
simultaneously in the operation
state.
TEST
Operation is stopped and refrigerant is passed through
the indoor unit to remove the outdoor unit frost
(defrosting operation) or to recover the refrigerant oil
(oil recovery operation). The indoor unit stops in about
5-10 minutes.
The fan stops and the refrigerant
passes through. The red lamp
flashes slowly.
DEFROST
The fan is stopped to prevent blowing out of cold air
when the machine is still not warm at the start of
heating operation. About 3 minutes are necessary.
The fan stops and the red lamp
lights steadily.
When the room temperature at heating operation reaches
the set temperature, the FAN is stopped and room
temperature rise is prevented. At this time, the fan is
operated periodically to detect the room temperature.
(4 minutes stop, 1minute operate)
The fan continues to operate and
the red lamp lights steadily.
When an [AUTO], [FAN] and an operation other than the
operation another indoor unit is already performing at
cooling/heating selection type or [HEAT] operation at a
cooling only unit is commanded, operation cannot be
performed at that setting.
Buzzer buzzes 5 times and setting
is not received. Operation before
setting continues.
After cooling operation stops, the drain pump is
operated. Remains for 3 minutes.
Flowing liquid
sound during
operation
A sound changed by the refrigerant flow may be made
by operation of another indoor unit connected to the
same outdoor unit. A switching sound may be made at
the start and after the end of defrosting operation and
oil recovery operation.
Squeaking sound
This is due to expansion and contraction of resin parts
by the temperature change during heating operation
and oil recovery operation.
Switching sound
A sound is generated when the internal valve is
switched at operation switching and at the start
of defrosting operation and oil recovery operation.
Makes a sound even after operation
stops.
Makes a sound
while operating.
Fan turns on/off periodically.
RUN signal is input, but is not
accepted. Buzzer sounds.
Operation
Red and green lamps flash
alternately.
Red lamp flashes.
Indoor unit fan does not operate
even through the RUN signal has
entered.
From the standpoint of control, the following operations are incorporated for air conditioner operation
and protection. They do not indicate trouble.
Operation not trouble
When operation and indication other than the above occurs, call the manager.
6-5 CASES SUCH AS THESE ARE NORMAL
06-43
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...