Check Point 1: Check Circuit connection
Check Point 1: Check Circuit connection
Check the connection of connector CN14
Check Point 2: Check Solenoid Coil
Check Point 2: Check Solenoid Coil
Remove CN14 and check the resistance value of coil in
the motor
If the resistance value is abnormal, replace Control PCB
If there is a temperature difference between Strainer terminals, there is a possibility of clogging .Check the temperature
difference.
And check the movement of inside dirty by changing the operation mode from Cooling to Heating, or from Heating to Cooling.
Option Parts. UTR-EV2, UTR-EV3
140
BROWN BLUE
BROWN YELLOW
300
ORANGE –
–
–
–
–
–
WHITE
140
RED ORANGE
RED WHITE
300
BLUE YELLOW
Resistance Value
Read Wire
Pipe (In)
Pipe (Out)
Hi TEMP.
Normal TEMP.
CLOSE
Example : Hot GUS
Pipe (In)
Pipe (Out)
Hi TEMP.
Hi TEMP.
OPEN
Example : Hot GUS
Check Point 6:
Check Point 6:
Check Operation of solenoid valve, check Open / Close operation
Check Operation of solenoid valve, check Open / Close operation
by temperature difference
by temperature difference
Pipe (In)
Pipe (Out)
Check Point 7:
Check Point 7:
Check clogging of strainer
Check clogging of strainer
Pipe (In)
Pipe (Out)
Check Point 5: Check the sound when power is turned ON
Check Point 5: Check the sound when power is turned ON
Check the magnetized sound by the initial operation when power is turned on.
If its sound does not appear, replace Control PCB.
Check Point 4: Check voltage of Control PCB
Check Point 4: Check voltage of Control PCB
Remove CN17, and check DC+12V Input voltage.
If there is 0V, replace main PWB.
Check Point 3: Initialize of Positioning
Check Point 3: Initialize of Positioning
Turn off the power source of PCB of the outdoor unit to
initialize the EEV for several times.
CN14
06-53
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...