Estimated details
Estimated details :
1.EV
1.EV
–
–
KIT (Open excessively) 4. Normal Function
KIT (Open excessively) 4. Normal Function
2.Installed piping
2.Installed piping
1) Refrigerant flow sound
1) Refrigerant flow sound
3.Indoor unit
3.Indoor unit
2) Defrost operation
2) Defrost operation
1)Installation
1)Installation
2)FAN & FAN MOTOR
2)FAN & FAN MOTOR
Check Point 1: EV - KIT (Open excessively)
Check Point 1: EV - KIT (Open excessively)
When the EV-kit Valve is open excessively, other indoor units
may not operate at full capacity or a loud refrigerant rushing
sound may be generated.
Turn off the power source of PCB of the indoor unit to initialize
the EV-KIT for several times.
Put 3 minute interval between each initializations. The EV-KIT
VALVE may return to normal.
Check EV-KIT (SERVICE INFORMATION)
6. ABNORMAL SOUND IS
HEARD FROM INDOOR UNIT
Check Point 2:
Check Point 2:
Installed piping
Installed piping
When the liquid Pipe diameter is large, a refrigerant rushing
sound will be generated and when the diameter is small,
capacity will be insufficient.
Check the design of piping installation
Check Point 3
Check Point 3
-
-
1:
1:
Installation
Installation
Check if sound will stop, when touch the unit by the hand.
Check installation of indoor unit.
Check the grill contact with the chassis.
Check Point 3
Check Point 3
-
-
2:
2:
FAN & FAN MOTOR
FAN & FAN MOTOR
Check contact of casing with a fan.
Check the contact of the shaft of the fan.
Normal Function
Normal Function
:
:
Refrigerant flow sound
Refrigerant flow sound
During operation and immediately after stopping the unit, the sound of water flowing in the air conditioners
piping may be heard. Also, noise may be particularly noticeable for about 2 to3 minutes after starting
operation (Sound of refrigerant flowing)
Normal Function
Normal Function
:
:
Defrost operation sound
Defrost operation sound
During heating operating, a sizzling sound may be heard occasionally. This sound is defrost operation.
06-42
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...