08-03
Be careful not to mix moisture and
contamination into the pipe
Moisture and contamination
in the pipe is a cause of trouble.
Air purge
Always use a vacuum pump to purge air.
Refrigerant charge
Do it always from the liquid phase
side.
Don't charge from the gas phase side.
Compressor oil is changed (Enclosed amount : 1700cc)
Be careful to handle synthetic oil, since it resolves easily by moisture and contamination.
Don't mix new synthetic oil and mineral oil.
It may cause trouble.
Using specified synthetic oil (POE oil:
MEL56(for J series)
),
since HFC refrigerant doesn't dissolve in mineral oil (for R22).