01-03
MANUAL AUTO
(5) Press the START/STOP button and make sure the
beeping sound is heard.
(1) Press the SLEEP button.
(1) Press the Manual Auto Button 3 sec.
(2) Press the ACL button.
OPERATION
(RED)
TIMER
(GREEN)
CORRECT : Pi PiPiPiPiPi
WRONG: Pi
(3 sec)
ACL
01
02
03
01
4. Check Address setting
5. Completion of Address setting mode
6. Setting up each Indoor unit
continuously
Flashing times of
address numbers
Operation lamp
turns off
Timer lamp keep blinks the number of times of address No.
"2" is needed when custom
code is different.
Address can be checked
by the number of blinking
of Timer Lamp.
After pressing the ACL
button, please set the
custom code again
if b,c,d setting.
7. Reset the power after setting up address of all Indoor units.
*
If the reset is not performed, address can not be read in normally.
(6) Indoor unit is displayed address number.
ON
OFF
(Example) ADDRESS : 03
OPERATION
LAMP
(RED)
ON
OFF
TIMER
LAMP
(GREEN)
PiPi
Pi PiPiPi
PiPi
PiPi
Repeat the "1" "5" operation.
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...