3) Simple remote controller
Stop the indoor and outdoor units. Push the remote controller
SET
button and
button
simultaneously for more than three seconds. The air conditioner will start to conduct a test
run and " " will display on the temperature display.
display.
However the
setting button does not have function but all other buttons,
displays and protection functions will operate.
To stop test running press the
button of the simple remote controller.
For the operation method refer to the operating manual and perform operation check.
Check that there are no abnormal sounds or vibration sounds during test run operation.
01-08
1) When the test run signal is transmitted from standard wired, wireless remote controller, simple remote controller
and central remote controller.
(1) The test runn operation starts and the electric expansion valve is controlled to a maximum flow, regardless of
the temperature condition.
(2) De-frosting and frost prevention operation has priority over item(1).
(3) After 60 minutes passes, the test run stops.
2) When the test run signal is transmitted from the outdoor unit.
(1) Whether state of the indoor unit operates or stops, All units in the same refrigerant system will start to conduct a
test run in accordance with the operation mode set by DIP SW 1-1 or SW 1-2 of outdoor unit ( see 1 - 3 - 1 ).
(2) Test running initialization is shown below.
Fan speed
Hi
Hi
Room Temperature Indication
18
30
Vertical Air Direction Panel
Horizontal Air Direction Panel
Swing
Operating Mode
Cooling
Heating
OFF
OFF
1-4 TEST RUN CONTROL
Position 1
Position or
4
6
Position 3
Position 3
Please refer to "5-4 LOUVER CONTROL" in this manual and find the definition
for air direction panel position.
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...