05-09
5-6-2 Auto Restart
(1) The air conditioner restarts with the previous setting operation.
(2) When the air conditioner restarts for heating operation, the "COLD AIR DISCHARGE PREVENTION FUNCTION"
operates.
5-6-3 Icing Protection Control
The icing of the indoor heat exchanger is prevented during the cooling and dry mode operation.
(1) Starting Condition
Heat exchanger middle temperature =< T
A
Comperessor is operation more than 10 minutes.
(2) Operation
EEV is fully opened.
Fan is at the setting amount.
(3) Completing Condition
Heat exchanger middle temperature >= T
B
After more than 5 minutes
*
Drain pump turns off at 60 minutes past the completion of the icing protection operation.
T
A
and T
B
are selected by DIP-SW.
DIP-SW 5-3
T
A
T
B
OFF
ON
1
4
7
8
5-6-4 Cold Air blowing protection control
During the heating operation, the cold air blowing is protected.
The indoor fan operation is limited at the starting the heating mode when the heat exchanger middle temperature
is higher than 27 C.
5-6-5 Defrosting Operation, Oil Recovery Operation
[Defrosting Operation] : It prevents the heating capacity decrease due to the adhered ice on the outdoor heat
exchanger.
[Oil Recovery Operation] : It periodically returns the residual refrigerantion oil in the indoor unit and the connection
piping back to the outdoor unit, and prevents the compressor oil level from decreasing.
Indoor Unit LED : Operation LED
3 sec ON 1 sec OFF
Blinking
Indoor Fan : Stop
Indoor EEV : Control pulse
*
During the above operation, a refrigerant noise may be heard from the indoor unit.
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...