1. TEST RUN
1-1 PRE SETTING
01-01
1-1-1 Custom code setting
A B C D
A B C D
Indoor
unit
Confusion
Remote
controller
Code change
When changing the custom code, follow the instruction below
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set)
DIP SW 5 - 1
DIP SW 5 - 2
A (Primary setting)
OFF
OFF
B
ON
OFF
Table
C
OFF
ON
D
ON
ON
Custom code
SW
1
SW
2
SW
3
SW
4
SW
5
ON
OFF
SW5-1
SW5-2
SW5-3
SW5-4
DIP SWITCH (SW1 ~ SW5)
Example : SW5
CUSTOM CODE SETTING FOR INDOOR UNIT
AU TYPE
AS 18 - 30 TYPE
AR TYPE
SW5
SW1
SW3
SW2
SW4
Jumper wire (JM2)
JM 1
Connect
Disconnect
Connect
Disconnect
Remote controller
custom code
A (Primary setting)
B
C
D
Table
Jumper wire
JM 2
Connect
Connect
Disconnect
Disconnect
Jumper wire (JM1)
AS 7-14 TYPE
CUSTOM CODE SETTING FOR WIRELESS REMOTE CONTROLLER
1
2
3
4
START/STOP
MASTER
CONTROL
MASTER
CONTROL
Press until only the clock is
displayed.
Press for more than 5 seconds
to display the current custom
code. (Initially set to )
Change the custom code be-
tween
to match the
code on the display to the air
conditioner custom code.
Press again to return to the
clock display. (The custom
code will be changed.)
NOTES
(1) If no buttons are pressed within 30 seconds after the custom code is displayed, the system returns to the original clock display.In this case, start
again from step 1.
(2) The remote controller resets to custom code A when the batteries in the remote controller are replaced. If you use a custom code other than custom
code A, reset the custom code after replacing the batteries.
If you do not know the air conditioner custom code setting, try each of the custom codes (
) until you find the code which operates the air
conditioner.
MASTER
CONTROL
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...