Detective Actuators:
Detective Actuators:
Discharge temperature thermistor
Detective details:
Detective details:
When discharge temperature sensor detected over 115 deg C during the
pump – down operation.
Releasing condition : Pump –
–
Down Dip SW On OFF
Pump Down Complete
Trouble shooting 16
OUTDOOR UNIT
OUTDOOR UNIT
Error Method:
Error Method:
PUMP DOWN ABNORMAL
(Discharge Temp. Abnormal )
Check Point 1 : Check Out of Gas or Gas Leak of Refrigerant
Check Point 1 : Check Out of Gas or Gas Leak of Refrigerant
Conduct Leak Check at Piping connection.
Check if the refrigerant amount is proper by measuring Gas pressure.
(Condensation temp., Refrigerant Pressure Chart) Refer to Service manual 8-4-2
Check Leak portion.
SEALING TEST
Charge the piping with nitrogen to the sealing test pressure (4.15Mpa).
After 24 hours, check that pressure has not fallen.
Note: When the ambient temperature changes by 5 deg, the test pressure changes about 0.07Mpa
When the refrigerant is recharged, make sure to perform the vacuuming and charge the originally specified amount.
Check Point 4 :
Check Point 4 :
Check for Outdoor Unit fan, control PCB
Check for Outdoor Unit fan, control PCB
Check the fan hand and check if it turns normal.
Check around Outdoor fan motor
(Parts Information 6)
(Parts Information 6)
Check if the air flow route of Outdoor unit fan is blocked.
If Outdoor fan motor is defective, replace it.
Check Point 2 :
Check Point 2 :
Error detection by defective mounting thermistor or cut off
Error detection by defective mounting thermistor or cut off
Thermistor came off the holder
Check if the cable is caught in etc,
Check the thermistor characteristics
Trouble shooting 17
Trouble shooting 17
If the thermistor is abnormal, replace the thermistor
Check Point 6 : Check EV - KIT
Check Point 6 : Check EV - KIT
Check around EV - KIT
(PARTS INFORMATION 11)
(PARTS INFORMATION 11)
Replace EV - KIT if it is defective.
Check Point 3 :
Check Point 3 :
SV2 (Bypass valve) operation defective
SV2 (Bypass valve) operation defective
Check the connection of SV2 (CN5)of control PCB.
Check around SV2 (Bypass Valve)
(Parts Information 7)
(Parts Information 7)
If either SV2 or Coil was abnormal, replace it.
Check Point 7 : Check valve opening
Check Point 7 : Check valve opening
If the 3 way valve (Gas pipe side) was closed, open it and
check the condition.
Forecast of Cause
Forecast of Cause:
1. Leak of refrigerant
5. EEV operation defective
2. Error detection by defective mounting of
6. EV - KIT operation defective
thermistor or cut off.
7. 3 way valve(Gas Side Pipe) was closed
3. SV2 operation defective
4. Check for Outdoor Unit fan
Check Point 5 : Check Outdoor unit EEV1
Check Point 5 : Check Outdoor unit EEV1
Check around Outdoor unit EEV1
(PARTS INFORMATION 10)
(PARTS INFORMATION 10)
If Outdoor unit EEV1 is defective , replace it
Indicate or Display:
Indicate or Display:
Indoor Unit :
Operation LED
Flash
Flash
,
,
Timer LED
3 Times Blink
3 Times Blink
Swing LED
3 Times Blink
3 Times Blink
Outdoor Unit :
LED1
Flash
Flash
,
,
LED2
10
10
Time
Time
s
s
Blink
Blink
ERROR CODE: E:32
06-20
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...