Check Point 1: Check connector of CT
Check Point 1: Check connector of CT
SERVICE PARTS INFORMATION 1
SERVICE PARTS INFORMATION 1
Current trance
RED
Controller PWB
Filter PCB
Current trance
Check the connection of connector CN202,CN11
CN202
CN202
Filter PCB
Check Point 2: Resistance value of CT
Check Point 2: Resistance value of CT
Check the terminal resistance of CT
CN11 to controller PWB
Resistance value
110 (about)
If the resistance value value is abnormal,
replace Filter PCB.
P/No.
9705256019 (Filter PCB)
6- 6 SERVICE PARTS INFORMATION
06-44
Check Point 3: Check voltage of CT detection current (Reference)
CN202
Filter PCB
Controller
PCB
CN11
Voltage value
( mV)
Detection
Current (A)
400
561
737
948
1187
5.6
6.9
8.4
10.0
12.0
Voltage value
( mV)
Detection
Current (A)
1525
1721
1971
2231
2495
14.7
16.2
18.2
20.2
22.3
2720
3001
3246
24.0
26.1
28.0
The value of the measured result is a reference value.
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...