5. INDOOR UNIT OPERATION
05-01
Fan speed zone
Hi zone
Med zone
Low zone
When the room
temperature decreases
When the room
temperature increases
2) HEATING OPERATION
3) DRY OPERATION
An example for heat operation
Indoor heat
exchanger
temperature (T
HE
)
Indoor fan speed
mode
47
41
HI
MED
LOW
OFF
(2)
(1)
(3)
TIME -->
2min.
2min.
2min.
2min.
T
HE
1) COOLING OPERATION
• Expansion
•
valve
• Indoor fan
motor
ON
OFF
OPEN
CLOSE
ON
ON
ON
ON
ON
ON
ON
ON
30s
30s
5s
3min
5s
3min
The indoor fan always rotates at "Lo" speed.
TIME -->
•
•
2
T
R
-T
S
1
2
T
R
-T
S
1
T
R
-T
S
2
T
R
-T
S
2
3
T
R
-T
S
3
T
R
-T
S
(1) When the T
S
is changed.
(2) When the operation mode is changed from other mode to "COOL".
(3) When the fan control is changed from other position to "AUTO".
The fan speed is determined automatically in accordance
with the condition "(T
R
(corrected room temperature) - T
S
(corrected set temperature)" as shown on the right.
However, the fan speed zone is determined in the manner
as the room temperature increases for the following cases.
2min.
(1) The indoor fan starts operation 5 seconds after the electric expansion valve opens. However, when the indoor unit just starts
its operation or the operation mode is changed from other to "DRY" and the refrigerant circulation is not stopped, the fan will
rotate immediately without a delay time of 5 seconds.
(2) The indoor fan will stop in 30 seconds when the refrigerant circulation stops.
(3) The indoor fan will stop immediately when the indoor unit is stopped by pushing the stop button or by a setting of ON timer.
(4) When the refrigerant circulation is stopped due to a lower room temperature for more then 3 minutes, the fan will rotate
2 minutes at intervals of 3 minutes.
(5) When the indoor unit just starts its operation or the operation mode is changed from other to "DRY" and the refrigerant
circulation is stopped, the fan will rotate for 1 minute and then it will operate according to the statement (4).
2min
(1) When the indoor heat exchanger temperature reaches 47 or more, the fan speed switches to the next higher position.
("LOW" --> "MED", "MED" --> "HIGH").
(2) When the indoor heat exchanger temperature drops below 41 while the refrigerant circulation of the indoor unit is ON,
the fan speed switches to the next lower position ("HIGH" --> "MED", "MED" --> "LOW").
(3) After switching the fan speed, it does not switch again within 2 minutes.
(4) When "FAN CONTROL" is switched from a set fan speed to "AUTO" after the cold air prevention is released , the fan of
indoor unit will start at "MED" speed for T
HE
or at "LOW" speed for T
HE .
41
41
5-1 FAN CONTROL
5-1-2 "AUTO" Position
AUTO
HIGH
MED
LOW
Press the FAN CONTROL button to set the fan speed.
Fan speed setting
5-1-1 Fan Speed Setting
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...