Pressure SW
Check Point 1: Check Circuit connection
Check Point 1: Check Circuit connection
Check the connects CN19, CN20, and each terminal connection at SW side (inside the insulation material)
Remove the connector and check continuity between terminals. Normal (When pipe is connected) : SHORT
Check Point 2: Check the power supply voltage to Pressure SW
Check Point 2: Check the power supply voltage to Pressure SW
If DC+5.0V does not appear,replace Control PCB
Check the voltage DC+5.0V between 1 - 2 of CN19 or CN20.
Hi pressure
Hi pressure
Lo pressure
Lo pressure
ON : 0.35 0.05Mpa
OFF: 0.2 0.05Mpa
OFF: 4.2 0.1Mpa
ON : 3.2 0.15Mpa
P/No.
9900187019 (Hi pressure SW)
P/No.
9900187019 (Lo pressure SW)
06-50
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...