1-1 Test run ( cooling & Heating )
All the indoor units connected to the outdoor unit can be test-operated by DIP switch setting.
SELECTOR SWITCH FOR TEST RUN AND NORMAL OPERATION
1-2 Pump down operation
Pump down operation is set with SW1- 3
1-3 Forced oil recovery operation
PUMP DOWN OPERATION
FORCED OIL RECOVERY OPERATION
2-1 Silent operation mode
For a reduction of noise level at night, the operating mode of the outdoor unit can be switched.
(In the cooling mode only.)
SILENT OPERATION MODE
Silent operation mode
Release
SW 2-1
ON
Operate
OFF
2-2 SW 2-2
DIP SW 2-2 setting Forbidden
SW2-2
OFF
SW1-2
SW1-1
Test Run
Remarks
OFF
OFF
Normal operation
OFF
ON
Cooling test run
SW1-1 / SW1-2 : OFF / OFF or ON / ON ON / OFF
ON
OFF
Heating test run
SW1-1 / SW1-2 : OFF / OFF or ON / ON ON / OFF
ON
ON
Normal operation
SW1-3
Pump down operation
Remarks
OFF
Release
ON
Operate
OFF ON and be kept at ON
position for more than 40 sec.
SW1-4
Forced oil recovery operation
Remarks
OFF
Release
ON
Operate
(
Factory setting)
(
Factory setting)
(
Factory setting)
(
Factory setting)
DIP SWITCH SETTING
(1) SW1 setting
(2) SW2 setting
Forced oil recovery operation is set with SW1- 4
OFF ON and be kept at ON
position for more than 10 sec.
2-3-2 OUTDOOR UNIT
02-16
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...