Trouble shooting 3
INDOOR UNIT
INDOOR UNIT
Error Method:
Error Method:
MODEL INFORMATION ABNORMAL
Indicate or Display:
Indicate or Display:
Indoor Unit :
Operation LED
Flash
Flash
,
,
Timer LED
Flash
Flash
Swing LED
OFF
OFF
Outdoor Unit :
LED1
Flash,
LED6
1 8TIMES Blink(Indoor Unit address)
ERROR CODE :
E:02
E:02
Detective Actuators:
Detective Actuators:
Circuitry in indoor unit Control PCB
Detective details:
Detective details:
When power is turned on, EEPROM read ERROR has been occurred
(2times matching read Test is failed for 3 times in a row),or the model
information that was read in from EEPROM has an apparent error.
Model information, which is memorized in EEPROM is recovered normally.
Forecast of Cause
Forecast of Cause : 1 .Power supply circuit (Voltage drop / Noise) 2.Indoor unit electrical parts defective
Check Point 1 : Check Power supply
Check Point 1 : Check Power supply
Check external cause (Power supply)
Instant Drop
Check if there is an electric equipment with a large load in the same circuit.
Instant Power Outage
Check if there is a defective contact or leakage in the power supply.
Noise
Check if there is any equipment that cause the harmonic wave near the power line.
(Neon tube or Electric equipment that harmonic wave Check that the grounding is completely insulated.)
Check Point 2 :
Check Point 2 :
Indoor unit electrical parts defective
Indoor unit electrical parts defective
Check connection / removal / incorrect wiring of all the connectors.
Check if short mark or corrosion is on PCB
Replace Control PCB and set up the original address,then check the
normal operation.
06-08
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...